2008-12-27 11:47:58REVIEW #: 1ST
 ACTION: DENIED
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ENERGY CALCULATIONS: BOTH A METHOD A AND A METHOD B
 CALCULATION WERE SUBMITTED FOR THIS PROJECT.
 NONRESIDENTIAL BUILDINGS WHICH WILL BE FINISHED IN
 SECTIONS AT A TIME AFTER CONSTRUCTION OF THE SHELL
 SHALL COMPLY WITH EITHER METHOD B OR C OF SUBCHAPTER
 13-4 OF THE CODE PRIOR TO GRANTING OF A PERMIT TO BUILD
 IN ACCORDANCE WITH FBCB 13-101.1.6. ALL ASSUMPTIONS
 MADE ABOUT FEATURES NOT INSTALLED UNTIL LATER THAT ARE
 NOT ON THE BUILDING PLANS SHALL BE LISTED AND APPENDED
 TO THE COMPLIANCE FORM SUBMITTED TO THE BUILDING
 DEPARTMENT IN ACCORDANCE WITH THIS SECTION. PROVIDE
 METHOD B OR C CALCULATIONS FOR THE ENTIRE BUILDING WITH
 APPENDED ASSUMPTIONS FOR UNFINISHED PORTIONS OF THE
 BUILDING.
  
 2. ENERGY CALCULATIONS: THE METHOD B CALCULATIONS
 INDICATE THEY WERE PREPARED BY "ARTHUR SLACK." ENERGY
 CODE CALCULATIONS SHALL BE MADE A PART OF THE PLANS AND
 SPECIFICATIONS OF THE BUILDING. THE BUILDING OFFICIAL
 SHALL REQUIRE THAT PLANS AND SPECIFICATIONS BE PREPARED
 BY AN ENGINEER OR ARCHITECT LICENSED TO PRACTICE IN THE
 STATE OF FLORIDA IN ACCORDANCE WITH FBCB 13-103.2. THIS
 MEANS THE PREPARER OF THE ENERGY CALCULATIONS SHALL BE
 PREPARED BY AN ARCHITECT, ENGINEER, INSTALLING
 MECHANICAL CONTRACTOR OR FLORIDA CERTIFIED COMMERCIAL
 ENERGY RATER. NO LICENSE INFORMATION COULD BE FOUND FOR
 ARTHUR SLACK ON THE ENERGY CALCULATIONS OR THE FLORIDA
 DBPR WEBSITE. FRED POPPER MAY SERVE AS THE PREPARER,
 DESIGNER OF RECORD AND OWNER/AGENT UNDER THESE
 SECTIONS. IT IS NOT CLEAR WHAT PART MR. GORDON BUCK
 PLAYS IN THE PREPARATION OR CERTIFICATION OF THESE
 CALCULATIONS.
  
 3. PAGE M-1: FLOOR PLAN SHOWS RETURN AIR GRILLS IN
 CEILING OF OFFICE A110 AND LAB A111 BUT REFLECTIVE
 CEILING PLAN ON A102 SHOWS ONLY SUPPLY REGISTERS.
 PLEASE COORDINATE PLANS SHOWING COMPLIANCE WITH THE
 REQUIREMENTS OF FBCM 601.4 AND 603.1.
  
 4. PAGE M-1: THE EXTERIOR WALL O.A. INTAKE CALLS FOR
 350 CFM WHILE THE OA CALCULATIONS ON M-2 CALL FOR 400
 TOTAL CFM. ALSO, AHU-2 IS SHOWN ON FLOOR PLAN TO BE
 BALANCED FOR 50 CFM OF O.A., NOT THE 100 CFM SHOWN ON
 THE O.A. CALCULATIONS SCHEDULE. PLEASE COORDINATE FLOOR
 PLANS WITH SCHEDULE IN ACCORDANCE WITH FBCM 603.1.
  
 5. PAGE M-1: O.A. INTAKE SHOWS MANUAL DAMPERS AND
 DETAIL ON M-2 CALLS FOR OPPOSED BLADE BALANCING DAMPERS
 WHILE NOTE ON EQUIPMENT SCHEDULE CALLS FOR MOTORIZED
 DAMPER AS REQUIRED PER FBCB 13-409.1.ABC.3.2. NO
 MOTORIZED DAMPER IS SHOWN ON FLOOR PLAN. PLEASE
 COORDINATE PLANS, SCHEDULES AND DETAILS TO SHOW
 COMPLIANCE WITH THIS SECTION.
  
 6. PAGE M-1: FLOOR PLAN CALLS FOR TWO LOUVERS INSTALLED
 AT O.A. INTAKES. LOUVERS ARE DEFINED AS PANEL WALLS IN
 ACCORDANCE WITH FAC RULE 9B-72. PROVIDE PRODUCT
 APPROVALS FOR THESE LOUVERS APPROVED IN WRITING BY THE
 DESIGNER OF RECORD IN ACCORDANCE WITH FBCB 106.3.3.
  
 7. PAGES M-1 AND M-2: THE SYMBOLS SHOWN ON THE SYMBOL
 LEGEND DO NOT CORRESPOND WITH THE ONES USED ON THE
 FLOOR PLAN. FOR AN EXAMPLE: SEE THE SYMBOL USED FOR THE
 DUCT MOUNTED SMOKE DETECTOR. PLEASE CLARIFY AND
 COORDINATE FLOOR PLAN WITH SCHEDULE IN ACCORDANCE WITH
 FBCB 106.1.1.
  
 8. PAGE M-2: THE O.A. CALCULATIONS SCHEDULE STATES "AS
 PER... TABLE 2." NO TABLE 2 COULD BE FOUND IN ASHRAE
 62.1-2004. PLEASE CLARIFY. THE DESIGN OUTDOOR AIRFLOW
 REQUIRED IN THE BREATHING ZONE OF THE OCCUPIABLE SPACE
 SHALL BE CALCULATED IN ACCORDANCE WITH CALCULATION 6-1
 USING TABLE 6-1 IN ACCORDANCE WITH FBCM 403.4 AND
 ASHRAE 62.1-2004 SECTION 6.2.2.1.
  
 9. PAGE M-2: NOTE #9 CALLS FOR REFRIGERANT PIPING TO BE
 CHARGED WITH R-22 WHILE THE A/C SCHEDULE CALLS FOR THE
 USE OF R410A. THE REFRIGERANT SHALL BE THAT WHICH THE
 EQUIPMENT OR APPLIANCE WAS DESIGNED TO UTILIZE OR
 CONVERTED TO UTILIZE IN ACCORDANCE WITH FBCM 1102.2 AND
 FBCM 304.1. PLEASE CLARIFY TO DEMONSTRATE COMPLIANCE
 WITH THESE SECTIONS.
  
 10. PAGES M-1 AND M-3: FLOOR PLAN SHOWS DUCT SMOKE
 DETECTOR AT AHU-1 INSTALLED ON SUPPLY (SEE COMMENT #7
 ABOVE) SIDE OF AHU WHILE THE DUCT DETECTOR DETAIL ON
 M-3 SHOWS THE DETECTOR BEING INSTALLED ON THE RETURN
 SIDE. PLEASE COORDINATE FLOOR PLAN WITH DETAIL AND SHOW
 COMPLIANCE WITH FBCM 606.2.1, WHICH REQUIRES THE
 DETECTOR TO BE IN THE SUPPLY AIR SYSTEM.
  
 11. PAGE M-3: THERE ARE THREE DIFFERENT DETAILS ON THIS
 PAGE WHICH SHOW DIFFERING CONFIGURATIONS OF THE
 AUXILIARY/SECONDARY DRAIN PROTECTION BEING PROVIDED AT
 THE AHU. SOME SHOW A SECONDARY DRAIN LINE FROM THE
 AUXILIARY DRAIN PAN AND SOME DO NOT. ALL OF THEM CALL
 FOR A WATER LEVEL DETECTION DEVICE. IF A SECONDARY
 DRAIN LINE IS TO BE USED, PLEASE SHOW THE TERMINATION
 LOCATION TO SHOW IT WILL TERMINATE AT A CONSPICUOUS
 LOCATION IN ACCORDANCE WITH FBCM 307.2.3(1).
 NOTE: THE SECONDARY DRAIN LINE IS NOT REQUIRED IF A
 WATER LEVEL DETECTION DEVICE IS INSTALLED IN/ON THE
 AUXILIARY DRAIN PAN IN ACCORDANCE WITH FBCM 307.2.3(3).
  
 12. PAGE M-3: THE DIFFUSER DETAIL ON THIS PAGE CALLS
 FOR FLEX DUCT TO BE SUPPORTED WITH 1 INCH STRAP. IN NO
 CASE SHALL THE MATERIAL SUPPORTING FLEXIBLE DUCT THAT
 IS IN DIRECT CONTACT WITH IT BE LESS THAN 1 1/2 INCHES
 WIDE IN ACCORDANCE WITH FBCM 603.5.6.6.
  
 13. PAGE M-3: THE ACCU DETAIL ON THIS PAGE CALLS FOR
 THE CU TO BE BOLTED "TO WITHSTAND 5 WINDS." PLEASE
 CLARIFY THE INTENT OF THIS STATEMENT, DEMONSTRATING
 COMPLIANCE WITH FBCM 301.13. ALSO, PROVIDE
 MANUFACTURER'S DATA SHOWING THESE OUTDOOR APPLIANCES
 ARE DESIGNED TO RESIST WIND PRESSURES IN ACCORDANCE
 WITH THIS SAME SECTION.
  
 14. PAGES M-2 AND E0: THE A/C EQUIPMENT SCHEDULE ON M-2
 CALLS FOR MOCP OF 15 AMPS FOR CU-2 WHILE THE PANEL
 SCHEDULE ON PAGE E0 CALLS FOR A 20 AMP BREAKER. PLEASE
 VERIFY WHICH OF THESE IS CORRECT AND PROVIDE THE
 CORRECTLY SIZED OCP BREAKER IN ACCORDANCE WITH FBCM
 304.1.
  