2008-12-27 11:47:58 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| REVIEWED FOR COMPLIANCE WITH THE FOLLOWING: |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. ENERGY CALCULATIONS: BOTH A METHOD A AND A METHOD B |
| CALCULATION WERE SUBMITTED FOR THIS PROJECT. |
| NONRESIDENTIAL BUILDINGS WHICH WILL BE FINISHED IN |
| SECTIONS AT A TIME AFTER CONSTRUCTION OF THE SHELL |
| SHALL COMPLY WITH EITHER METHOD B OR C OF SUBCHAPTER |
| 13-4 OF THE CODE PRIOR TO GRANTING OF A PERMIT TO BUILD |
| IN ACCORDANCE WITH FBCB 13-101.1.6. ALL ASSUMPTIONS |
| MADE ABOUT FEATURES NOT INSTALLED UNTIL LATER THAT ARE |
| NOT ON THE BUILDING PLANS SHALL BE LISTED AND APPENDED |
| TO THE COMPLIANCE FORM SUBMITTED TO THE BUILDING |
| DEPARTMENT IN ACCORDANCE WITH THIS SECTION. PROVIDE |
| METHOD B OR C CALCULATIONS FOR THE ENTIRE BUILDING WITH |
| APPENDED ASSUMPTIONS FOR UNFINISHED PORTIONS OF THE |
| BUILDING. |
| |
| 2. ENERGY CALCULATIONS: THE METHOD B CALCULATIONS |
| INDICATE THEY WERE PREPARED BY "ARTHUR SLACK." ENERGY |
| CODE CALCULATIONS SHALL BE MADE A PART OF THE PLANS AND |
| SPECIFICATIONS OF THE BUILDING. THE BUILDING OFFICIAL |
| SHALL REQUIRE THAT PLANS AND SPECIFICATIONS BE PREPARED |
| BY AN ENGINEER OR ARCHITECT LICENSED TO PRACTICE IN THE |
| STATE OF FLORIDA IN ACCORDANCE WITH FBCB 13-103.2. THIS |
| MEANS THE PREPARER OF THE ENERGY CALCULATIONS SHALL BE |
| PREPARED BY AN ARCHITECT, ENGINEER, INSTALLING |
| MECHANICAL CONTRACTOR OR FLORIDA CERTIFIED COMMERCIAL |
| ENERGY RATER. NO LICENSE INFORMATION COULD BE FOUND FOR |
| ARTHUR SLACK ON THE ENERGY CALCULATIONS OR THE FLORIDA |
| DBPR WEBSITE. FRED POPPER MAY SERVE AS THE PREPARER, |
| DESIGNER OF RECORD AND OWNER/AGENT UNDER THESE |
| SECTIONS. IT IS NOT CLEAR WHAT PART MR. GORDON BUCK |
| PLAYS IN THE PREPARATION OR CERTIFICATION OF THESE |
| CALCULATIONS. |
| |
| 3. PAGE M-1: FLOOR PLAN SHOWS RETURN AIR GRILLS IN |
| CEILING OF OFFICE A110 AND LAB A111 BUT REFLECTIVE |
| CEILING PLAN ON A102 SHOWS ONLY SUPPLY REGISTERS. |
| PLEASE COORDINATE PLANS SHOWING COMPLIANCE WITH THE |
| REQUIREMENTS OF FBCM 601.4 AND 603.1. |
| |
| 4. PAGE M-1: THE EXTERIOR WALL O.A. INTAKE CALLS FOR |
| 350 CFM WHILE THE OA CALCULATIONS ON M-2 CALL FOR 400 |
| TOTAL CFM. ALSO, AHU-2 IS SHOWN ON FLOOR PLAN TO BE |
| BALANCED FOR 50 CFM OF O.A., NOT THE 100 CFM SHOWN ON |
| THE O.A. CALCULATIONS SCHEDULE. PLEASE COORDINATE FLOOR |
| PLANS WITH SCHEDULE IN ACCORDANCE WITH FBCM 603.1. |
| |
| 5. PAGE M-1: O.A. INTAKE SHOWS MANUAL DAMPERS AND |
| DETAIL ON M-2 CALLS FOR OPPOSED BLADE BALANCING DAMPERS |
| WHILE NOTE ON EQUIPMENT SCHEDULE CALLS FOR MOTORIZED |
| DAMPER AS REQUIRED PER FBCB 13-409.1.ABC.3.2. NO |
| MOTORIZED DAMPER IS SHOWN ON FLOOR PLAN. PLEASE |
| COORDINATE PLANS, SCHEDULES AND DETAILS TO SHOW |
| COMPLIANCE WITH THIS SECTION. |
| |
| 6. PAGE M-1: FLOOR PLAN CALLS FOR TWO LOUVERS INSTALLED |
| AT O.A. INTAKES. LOUVERS ARE DEFINED AS PANEL WALLS IN |
| ACCORDANCE WITH FAC RULE 9B-72. PROVIDE PRODUCT |
| APPROVALS FOR THESE LOUVERS APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD IN ACCORDANCE WITH FBCB 106.3.3. |
| |
| 7. PAGES M-1 AND M-2: THE SYMBOLS SHOWN ON THE SYMBOL |
| LEGEND DO NOT CORRESPOND WITH THE ONES USED ON THE |
| FLOOR PLAN. FOR AN EXAMPLE: SEE THE SYMBOL USED FOR THE |
| DUCT MOUNTED SMOKE DETECTOR. PLEASE CLARIFY AND |
| COORDINATE FLOOR PLAN WITH SCHEDULE IN ACCORDANCE WITH |
| FBCB 106.1.1. |
| |
| 8. PAGE M-2: THE O.A. CALCULATIONS SCHEDULE STATES "AS |
| PER... TABLE 2." NO TABLE 2 COULD BE FOUND IN ASHRAE |
| 62.1-2004. PLEASE CLARIFY. THE DESIGN OUTDOOR AIRFLOW |
| REQUIRED IN THE BREATHING ZONE OF THE OCCUPIABLE SPACE |
| SHALL BE CALCULATED IN ACCORDANCE WITH CALCULATION 6-1 |
| USING TABLE 6-1 IN ACCORDANCE WITH FBCM 403.4 AND |
| ASHRAE 62.1-2004 SECTION 6.2.2.1. |
| |
| 9. PAGE M-2: NOTE #9 CALLS FOR REFRIGERANT PIPING TO BE |
| CHARGED WITH R-22 WHILE THE A/C SCHEDULE CALLS FOR THE |
| USE OF R410A. THE REFRIGERANT SHALL BE THAT WHICH THE |
| EQUIPMENT OR APPLIANCE WAS DESIGNED TO UTILIZE OR |
| CONVERTED TO UTILIZE IN ACCORDANCE WITH FBCM 1102.2 AND |
| FBCM 304.1. PLEASE CLARIFY TO DEMONSTRATE COMPLIANCE |
| WITH THESE SECTIONS. |
| |
| 10. PAGES M-1 AND M-3: FLOOR PLAN SHOWS DUCT SMOKE |
| DETECTOR AT AHU-1 INSTALLED ON SUPPLY (SEE COMMENT #7 |
| ABOVE) SIDE OF AHU WHILE THE DUCT DETECTOR DETAIL ON |
| M-3 SHOWS THE DETECTOR BEING INSTALLED ON THE RETURN |
| SIDE. PLEASE COORDINATE FLOOR PLAN WITH DETAIL AND SHOW |
| COMPLIANCE WITH FBCM 606.2.1, WHICH REQUIRES THE |
| DETECTOR TO BE IN THE SUPPLY AIR SYSTEM. |
| |
| 11. PAGE M-3: THERE ARE THREE DIFFERENT DETAILS ON THIS |
| PAGE WHICH SHOW DIFFERING CONFIGURATIONS OF THE |
| AUXILIARY/SECONDARY DRAIN PROTECTION BEING PROVIDED AT |
| THE AHU. SOME SHOW A SECONDARY DRAIN LINE FROM THE |
| AUXILIARY DRAIN PAN AND SOME DO NOT. ALL OF THEM CALL |
| FOR A WATER LEVEL DETECTION DEVICE. IF A SECONDARY |
| DRAIN LINE IS TO BE USED, PLEASE SHOW THE TERMINATION |
| LOCATION TO SHOW IT WILL TERMINATE AT A CONSPICUOUS |
| LOCATION IN ACCORDANCE WITH FBCM 307.2.3(1). |
| NOTE: THE SECONDARY DRAIN LINE IS NOT REQUIRED IF A |
| WATER LEVEL DETECTION DEVICE IS INSTALLED IN/ON THE |
| AUXILIARY DRAIN PAN IN ACCORDANCE WITH FBCM 307.2.3(3). |
| |
| 12. PAGE M-3: THE DIFFUSER DETAIL ON THIS PAGE CALLS |
| FOR FLEX DUCT TO BE SUPPORTED WITH 1 INCH STRAP. IN NO |
| CASE SHALL THE MATERIAL SUPPORTING FLEXIBLE DUCT THAT |
| IS IN DIRECT CONTACT WITH IT BE LESS THAN 1 1/2 INCHES |
| WIDE IN ACCORDANCE WITH FBCM 603.5.6.6. |
| |
| 13. PAGE M-3: THE ACCU DETAIL ON THIS PAGE CALLS FOR |
| THE CU TO BE BOLTED "TO WITHSTAND 5 WINDS." PLEASE |
| CLARIFY THE INTENT OF THIS STATEMENT, DEMONSTRATING |
| COMPLIANCE WITH FBCM 301.13. ALSO, PROVIDE |
| MANUFACTURER'S DATA SHOWING THESE OUTDOOR APPLIANCES |
| ARE DESIGNED TO RESIST WIND PRESSURES IN ACCORDANCE |
| WITH THIS SAME SECTION. |
| |
| 14. PAGES M-2 AND E0: THE A/C EQUIPMENT SCHEDULE ON M-2 |
| CALLS FOR MOCP OF 15 AMPS FOR CU-2 WHILE THE PANEL |
| SCHEDULE ON PAGE E0 CALLS FOR A 20 AMP BREAKER. PLEASE |
| VERIFY WHICH OF THESE IS CORRECT AND PROVIDE THE |
| CORRECTLY SIZED OCP BREAKER IN ACCORDANCE WITH FBCM |
| 304.1. |
| |