2008-12-24 08:52:16 | ** DENIED REVIEW** |
| |
| |
| |
| |
| 1) NOTE: PLEASE SEE FBC 13-106.1. THIS IS NOT A |
| COMPLETE BUILDING AS APPLIED. THE SUBMITTED ENERGY |
| CALCULATIONS ARE METHOD *A* FOR WHOLE BUILDING |
| COMPLIANCE WHICH MAY NOT BE USED. |
| PLEASE SEE THE SECTION ABOVE GIVEN WHICH CLEARLY GIVES |
| TWO POSSIBLE METHODS WHICH MAY BE USED. THE METHOD *A* |
| SUBMITTED FOR WHOLE BUILDING COMPLIANCE IS NOT CODE |
| COMPLIANT EVEN IF IT WERE POSSIBLE TO BE USED. NOT ALL |
| ITEMS IN THE INPUT DATA REPORT ARE COMPLETE. ONE |
| EXAMPLE WOULD BE EXTERIOR LIGHTING WHICH IS BLANK. |
| |
| 2) NOTE: PLEASE SEE SHEET A-104 AS THE BUILDING AS |
| SUBMITTED LENDS TO A BUSINESS OCCUPANCY NOT RETAIL AS |
| SHOWN ON THE SEPARATE SUBMITTED ENERGY CALCULATIONS |
| WHICH STATE BUILDING AS RETAIL. |
| PLEASE ADJUST. |
| PLEASE ALSO SEE THE SUBMITTED METHOD *B* IS ALSO |
| INCOMPLETE. ONE EXAMPLE IS EXTERIOR LIGHTING. |
| 13-415.2.ABC.1.1,.1.2 AND .1.3. |
| 13-400.B.3, 13-415.2.ABC.1.1,.1.2,.1.3. |
| ** THIS IS ONLY ONE EXAMPLE: THERE ARE OTHER ITEMS |
| WHICH ARE NOT CORRECT ON THE IDR>. |
| |
| ** ALSO METHOD *C* IS SHOWN ON PLANS FOR LIGHTING |
| COMPLIANCE. PLEASE SEE 13-415.2.ABC.1 AS MULTIPLE |
| METHODS OF CALCULATIONS IS NOT PERMITTED. |
| |
| 3) NOTE: THE METHOD *B* CALCULATIONS SUBMITTED CONTAIN |
| A PRINTED NAME FOR PREPARED BY * MR. ARTHUR SLACK*. THE |
| DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION DOES |
| NOT CONTAIN ANY LICENSE INFORMATION FOR SAID INDIVIDUAL |
| AS REQUIRED. |
| PLEASE SEE FBC 13-101.1 AS THE RESPONSIBLE DESIGNER OF |
| RECORD SHALL MEET LICENSING UNDER FLORIDA STATUTES |
| 471,481 AND 489 WHEN MEETING EXCEPTIONS. THIS |
| INDIVIDUAL AS SHOWN DOES NOT CONTAIN THE LICENSING AS |
| REQUIRED. THIS IS A COMMERCIAL BUILDING. PLEASE SEE FS |
| 481.029, 471.003. |
| PLEASE ALSO SEE THE LOCATION IN WHICH MECHANICAL |
| DESIGNER OF RECORD SHOULD BE CONTAINS A SIGNATURE AND |
| SEAL FROM MR. GORDON BUCK WHICH IS NOT ON RECORD AS THE |
| MECHANICAL OR ELECTRICAL DESIGNERS. SOME SETS HAVE THIS |
| INDIVIDUAL LISTED ON MULTIPLE LINES, USE OF WHITE OUT |
| ETC WHICH IS NOT PERMITTED. THESE DOCUMENTS ARE BEING |
| RETAINED BY THIS OFFICE. THE LICENSED STRUCTURAL |
| ENGINEER BEING LISTED AS THE MECHANICAL DESIGNER |
| SIGNING, AND SEALING ENERGY CALCULATIONS IS NOT |
| PERMITTED UNLESS MEETING REQUIREMENTS. |
| PLEASE SEE FS 471.025. PART 3. NOTED BELOW FORM THE |
| STATUTES. |
| (3) NO LICENSEE SHALL AFFIX OR PERMIT TO BE AFFIXED HIS |
| OR HER SEAL, NAME, OR DIGITAL SIGNATURE TO ANY PLAN, |
| SPECIFICATION, DRAWING, FINAL BID DOCUMENT, OR OTHER |
| DOCUMENT THAT DEPICTS WORK WHICH HE OR SHE IS NOT |
| LICENSED TO PERFORM OR WHICH IS BEYOND HIS OR HER |
| PROFESSION OR SPECIALTY THEREIN. |
| 3) NOTE: PLEASE COMPLETE RISER WITH ALL CONDUCTORS. |
| SOME OF THESE HAVE APPARENTLY BEEN HANDWRITTEN ON THE |
| PLAN WHICH IS NOT PERMITTED. THIS WILL NEED TO BE |
| REVISED WHEN MAKING OTHER CORRECTIONS. |
| FS 471.025. |
| FBC 106.5 |
| |
| 4) NOTE: PLEASE PROVIDE EQUIPMENT GROUNDING CONDUCTORS |
| AFTER THE FIRST MEANS OF DISCONNECT. THERE ARE NONE |
| SHOWN ON RISER? |
| PLEASE SEE 250.24, 250.6, 250.110, 250.122 ETC AS THESE |
| ARE REQUIRED AFTER THE 600AMP MAIN AS SHOWN. |
| PLEASE ALSO INDICATE THE REQUIRED FLOATING NEUTRAL KIT |
| AT METERS. |
| |
| 5) NOTE: PLEASE COORDINATE AIC RATINGS. SEE LP-1 WHICH |
| INDICATES 65K ON PANEL AND 22K ON RISER. |
| 110.9 |
| FBC 106.1.1 FOR COORDINATION AND CLARITY. |
| |
| 6) NOTE: PLEASE SEE NOTES ON PANEL WHICH INDICATE ALL |
| CONDUCTORS TO BE #12 UNLESS OTHERWISE NOTED. HOWEVER |
| ITEMS WHICH CONTAIN OVER CURRENT PROTECTION HIGHER THAN |
| 20AMPS ON PANEL SCHEDULE DOES NOT LIST ANY OTHER |
| CONDUCTOR SIZES. PLEASE COMPLETE PANEL SCHEDULES WITH |
| ALL CONDUCTOR SIZES PER 240.4, 310.16 ETC |
| FBC 106.3.5.1.2, 106.1.1 |
| |
| 7) NOTE: PLEASE PROVIDE MORE INFORMATION AND DETAILS |
| FOR LIGHTING CONTROLS. PLEASE SEE PLANS AS THERE WAS NO |
| SYMBOL LEGEND FOR WHAT MAY APPEAR TO BE DEVICES FOR |
| LIGHTING CONTROLS. |
| PLEASE SEE 13-415.1.ABC.1, .1.2, .1.3 AND .1.4. |
| NO INFORMATION SHOWN FOR EXTERIOR LIGHTING CONTROLS. |
| |
| 8) NOTE: THE VACANT FUTURE TENANT SPACE WILL BE |
| REQUIRED TO CONTAIN A EMERGENCY BACK UP LIGHT |
| FIXTURE(S) OF SOME SORT WIRED PER 700.12F AND 700.16. |
| NFPA1017.8,7.9. |
| |
| 9) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES |
| ARE LISTED ON THE PLANS. |
| FBC 2004 W/ 2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| |
| *** AS THERE IS INFORMATION NOT YET SUBMITTED THERE MAY |
| BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT |
| BE MADE AT THIS TIME. |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |