Plan Review Notes
Plan Review Notes For Permit 08110565
Permit Number 08110565
Review Stop E
Sequence Number 1
Notes
Date Text
2008-12-24 08:52:16** DENIED REVIEW**
  
  
  
  
 1) NOTE: PLEASE SEE FBC 13-106.1. THIS IS NOT A
 COMPLETE BUILDING AS APPLIED. THE SUBMITTED ENERGY
 CALCULATIONS ARE METHOD *A* FOR WHOLE BUILDING
 COMPLIANCE WHICH MAY NOT BE USED.
 PLEASE SEE THE SECTION ABOVE GIVEN WHICH CLEARLY GIVES
 TWO POSSIBLE METHODS WHICH MAY BE USED. THE METHOD *A*
 SUBMITTED FOR WHOLE BUILDING COMPLIANCE IS NOT CODE
 COMPLIANT EVEN IF IT WERE POSSIBLE TO BE USED. NOT ALL
 ITEMS IN THE INPUT DATA REPORT ARE COMPLETE. ONE
 EXAMPLE WOULD BE EXTERIOR LIGHTING WHICH IS BLANK.
  
 2) NOTE: PLEASE SEE SHEET A-104 AS THE BUILDING AS
 SUBMITTED LENDS TO A BUSINESS OCCUPANCY NOT RETAIL AS
 SHOWN ON THE SEPARATE SUBMITTED ENERGY CALCULATIONS
 WHICH STATE BUILDING AS RETAIL.
 PLEASE ADJUST.
 PLEASE ALSO SEE THE SUBMITTED METHOD *B* IS ALSO
 INCOMPLETE. ONE EXAMPLE IS EXTERIOR LIGHTING.
 13-415.2.ABC.1.1,.1.2 AND .1.3.
 13-400.B.3, 13-415.2.ABC.1.1,.1.2,.1.3.
 ** THIS IS ONLY ONE EXAMPLE: THERE ARE OTHER ITEMS
 WHICH ARE NOT CORRECT ON THE IDR>.
  
 ** ALSO METHOD *C* IS SHOWN ON PLANS FOR LIGHTING
 COMPLIANCE. PLEASE SEE 13-415.2.ABC.1 AS MULTIPLE
 METHODS OF CALCULATIONS IS NOT PERMITTED.
  
 3) NOTE: THE METHOD *B* CALCULATIONS SUBMITTED CONTAIN
 A PRINTED NAME FOR PREPARED BY * MR. ARTHUR SLACK*. THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION DOES
 NOT CONTAIN ANY LICENSE INFORMATION FOR SAID INDIVIDUAL
 AS REQUIRED.
 PLEASE SEE FBC 13-101.1 AS THE RESPONSIBLE DESIGNER OF
 RECORD SHALL MEET LICENSING UNDER FLORIDA STATUTES
 471,481 AND 489 WHEN MEETING EXCEPTIONS. THIS
 INDIVIDUAL AS SHOWN DOES NOT CONTAIN THE LICENSING AS
 REQUIRED. THIS IS A COMMERCIAL BUILDING. PLEASE SEE FS
 481.029, 471.003.
 PLEASE ALSO SEE THE LOCATION IN WHICH MECHANICAL
 DESIGNER OF RECORD SHOULD BE CONTAINS A SIGNATURE AND
 SEAL FROM MR. GORDON BUCK WHICH IS NOT ON RECORD AS THE
 MECHANICAL OR ELECTRICAL DESIGNERS. SOME SETS HAVE THIS
 INDIVIDUAL LISTED ON MULTIPLE LINES, USE OF WHITE OUT
 ETC WHICH IS NOT PERMITTED. THESE DOCUMENTS ARE BEING
 RETAINED BY THIS OFFICE. THE LICENSED STRUCTURAL
 ENGINEER BEING LISTED AS THE MECHANICAL DESIGNER
 SIGNING, AND SEALING ENERGY CALCULATIONS IS NOT
 PERMITTED UNLESS MEETING REQUIREMENTS.
 PLEASE SEE FS 471.025. PART 3. NOTED BELOW FORM THE
 STATUTES.
 (3) NO LICENSEE SHALL AFFIX OR PERMIT TO BE AFFIXED HIS
 OR HER SEAL, NAME, OR DIGITAL SIGNATURE TO ANY PLAN,
 SPECIFICATION, DRAWING, FINAL BID DOCUMENT, OR OTHER
 DOCUMENT THAT DEPICTS WORK WHICH HE OR SHE IS NOT
 LICENSED TO PERFORM OR WHICH IS BEYOND HIS OR HER
 PROFESSION OR SPECIALTY THEREIN.
 3) NOTE: PLEASE COMPLETE RISER WITH ALL CONDUCTORS.
 SOME OF THESE HAVE APPARENTLY BEEN HANDWRITTEN ON THE
 PLAN WHICH IS NOT PERMITTED. THIS WILL NEED TO BE
 REVISED WHEN MAKING OTHER CORRECTIONS.
 FS 471.025.
 FBC 106.5
  
 4) NOTE: PLEASE PROVIDE EQUIPMENT GROUNDING CONDUCTORS
 AFTER THE FIRST MEANS OF DISCONNECT. THERE ARE NONE
 SHOWN ON RISER?
 PLEASE SEE 250.24, 250.6, 250.110, 250.122 ETC AS THESE
 ARE REQUIRED AFTER THE 600AMP MAIN AS SHOWN.
 PLEASE ALSO INDICATE THE REQUIRED FLOATING NEUTRAL KIT
 AT METERS.
  
 5) NOTE: PLEASE COORDINATE AIC RATINGS. SEE LP-1 WHICH
 INDICATES 65K ON PANEL AND 22K ON RISER.
 110.9
 FBC 106.1.1 FOR COORDINATION AND CLARITY.
  
 6) NOTE: PLEASE SEE NOTES ON PANEL WHICH INDICATE ALL
 CONDUCTORS TO BE #12 UNLESS OTHERWISE NOTED. HOWEVER
 ITEMS WHICH CONTAIN OVER CURRENT PROTECTION HIGHER THAN
 20AMPS ON PANEL SCHEDULE DOES NOT LIST ANY OTHER
 CONDUCTOR SIZES. PLEASE COMPLETE PANEL SCHEDULES WITH
 ALL CONDUCTOR SIZES PER 240.4, 310.16 ETC
 FBC 106.3.5.1.2, 106.1.1
  
 7) NOTE: PLEASE PROVIDE MORE INFORMATION AND DETAILS
 FOR LIGHTING CONTROLS. PLEASE SEE PLANS AS THERE WAS NO
 SYMBOL LEGEND FOR WHAT MAY APPEAR TO BE DEVICES FOR
 LIGHTING CONTROLS.
 PLEASE SEE 13-415.1.ABC.1, .1.2, .1.3 AND .1.4.
 NO INFORMATION SHOWN FOR EXTERIOR LIGHTING CONTROLS.
  
 8) NOTE: THE VACANT FUTURE TENANT SPACE WILL BE
 REQUIRED TO CONTAIN A EMERGENCY BACK UP LIGHT
 FIXTURE(S) OF SOME SORT WIRED PER 700.12F AND 700.16.
 NFPA1017.8,7.9.
  
 9) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE LISTED ON THE PLANS.
 FBC 2004 W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 *** AS THERE IS INFORMATION NOT YET SUBMITTED THERE MAY
 BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT
 BE MADE AT THIS TIME.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  