2008-12-18 15:37:15BUILDING PLAN REVIEW
 PERMIT: 08110565
 ADD: 2112 N JOG RD
 CONT: POPPER AND ASSOCIATES
 TEL: (561)719-7133
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS, PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. 106.1* /2004
 SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE
 CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) MISSING SOILS REPORTS, SHEET S-0.1 FOUNDATION NOTE
 F-1 INDICATES TESTING LAB OF THE PALM BEACHES REPORT#
 07/118-02. PLEASE SUBMIT TWO ORIGINAL SIGNED AND SEALED
 REPORTS.
  
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 3) PROVIDE THE MINIMUM ENERGY INFORMATION FOR SHELL
 BUILDING,13-400.2.A.2 SHELL BUILDINGS. SHELL BUILDINGS
 SHALL COMPLY WITH THIS CODE BY METHOD B OR METHOD C.
 ONCE ALL ENERGY-RELATED DESIGN PARAMETERS ARE KNOWN,
 METHOD A CALCULATION MAY BE
 SUBMITTED. MINIMUM WALL, ROOF INSULATIONS, MECHANICAL
 EQUIPMENT AND ELECTRICAL FOR THE TOTAL BUILDING. SHEET
 M-1 INDICATES FUTURE TENANT SPACE NO MECHANICAL
 INFORMATION AS WELL AS SHEET E-1 MISSING ELECTRICAL FOR
 FUTURE TENANT AT THIS TIME WITH LIMITED ENERGY
 INFORMATION ONLY FORM B OR C MAY BE SUBMITTED.
  
 4) NOTE SHEET A-105 DETAIL 1, SECTION A-A , B-B AND
 DETAIL 1 SHEET A-106 ALL INDICATE THE USE OF R-19
 INSULATION LAID DIRECTLY UPON A ARMSTRONG SUSPENDED
 CEILING SYSTEM.
  
 13-404.1.ABC.1 ROOF/CEILING THERMAL ENVELOPES.
 THE ROOF OR CEILING WHICH FUNCTIONS AS THE BUILDING?S
 THERMAL ENVELOPE SHALL BE INSULATED TO AN R-VALUE OF AT
 LEAST R-10. ROOF INSULATION SHALL NOT BE INSTALLED ON A
 SUSPENDED CEILING WITH REMOVABLE CEILING PANELS.
  
 5) THE OTHER ISSUE THAT WILL TIE TO THE ENERGY
 CALCULATIONS VERSES THE PRODUCT APPROVAL FOR THE FLAT
 ROOF IS A DISCREPANCY. THE ENERGY CALCULATIONS DO
 INDICATE THE USE OF A BAR JOIST AND METAL DECK ROOFING
 SYSTEM WITH A R-19 BATT SYSTEM. IF METHOD ?C? IS CHOSEN
 PLEASE REVIEW THE PRESCRIPTIVE FOR METAL BUILDING ROOFS
 13-401.1.C.1.2.
  
 PLEASE ALSO REVIEW THE PRODUCT APPROVAL FOR THE FLAT
 ROOF SYSTEM, THE PRODUCT SUBMITTED NOA 07-0228.05 JOHN
 MANSVILLE BITUMEN ROOFING SYSTEMS OVER CONCRETE DECKS,
 PLEASE REVIEW DECK TYPE ALL INDICATE CONCRETE DECKS
 INSULATED, REQUIRING INSULATION ABOVE THE
 CONCRETE DECK AND THE SECOND ISSUE IS UNDER THE DECK
 DESCRIPTION ALL ARE 2500 PSI STRUCTURAL CONCRETE DECKS
 OR CONCRETE PLANK DECKS, NOT A METAL DECK AND BAR JOIST
 SYSTEM.
  
 6) IN THE NEW ENERGY CALCULATIONS PLEASE VERIFY THAT
 EXTERIOR DOOR OPENINGS ARE FILLED IN ON THE INPUT DATA
 REPORT, FORM IS LEFT BLANK. 13-403, DOORS.
  
 7) THE COVER SHEET INDICATES THE BUILDING TYPE AS A V-B
 FULLY SPRINKLED, THE INDEX DOES NOT INDICATE ANY FIRE
 SPRINKLER PLANS IN THE SET. 106.3.5.1.1(5) FIRE
 SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC FIRE
 SPRINKLERS.
  
 8) SHEET A-101 PLANS ARE NOT CLEAR AS TO IF THE
 ACCOUNTING OFFICE IS A SEPARATE TENANT OR IF THEY ARE
 THE ACCOUNTANT FOR THE DENTIST( BOOK KEEPING PART OF
 THE DENTAL BUSINESS). IF THE ACCOUNTANT IS A SEPARATE
 TENANT IT APPEARS THEY SHARE A COMMON RESTROOM. PLANS
 DO NOT INDICATE RATED TENANT SEPARATION WALLS.
 708.1(5). EXCEPTION# 1 DOES ALLOW FOR BUSINESS
 OCCUPANCIES NOT TO HAVE FIRE RESISTANCE RATINGS WHEN NO
 AREA BETWEEN FIRE PARTITIONS HAVING A 1-HOUR
 FIRE-RESISTANCE RATING EXCEEDS 3,000 SQ FT. THIS
 BUILDING HAS A NET FLOOR FOOT PRINT OF 3,200 SQ FT
 SOMEWHERE WITHIN THE STRUCTURE A FIRE PARTITION WILL BE
 REQUIRED.
  
 9) SHEET A-101 DOOR# 1-A100B & DOOR 2-A100B BOTH ARE
 MISSING THE 18? ON THE LATCH SIDE. 11-4.13.6.
 DOOR 1-A100B ALSO NEEDS TO REFER TO REVIEW 11-4.4.1
 PROTRUDING OBJECTS.
  
 10) SHEET A-101 DOOR# 1-A107-B SWINGS OVER 50% OF THE
 REQUIRED CORRIDOR. 1008.1.8.8
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR
 LANDING, WHEN FULLY OPEN.
  
 11) SHEET A-101FLOORPLAN DOES NOT INDICATE ANY STORAGE
 ROOMS FOR THE STORM SHUTTERS. THE DESIGNER HAS ELECTED
 TO USE STORM PANELS BUT NO STORAGE AREA IS LOCATED
 WITHIN THE BUILDING. PLEASE PROVIDE STORAGE ROOM AND
 THE FOLLOWING:
 PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT
 MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING IS DONE
 SUFFICIENTLY IN ADVANCE OF THE HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE
 ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST
 BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 IN LEAU OF LARGE MISSILE IMPACT RATED WINDOWS, STORM
 SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/
 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION.
  
 12) SHEET A-103 & S-3.0 INDICATES THE TYPE OF ROOFING
 SPECIFICATION TO BE USED ON THE FLAT ROOF DECK. THE
 DESIGNER OF RECORD IS REQUESTING A GAF ROOFING PRODUCT
 TO BE USED. SUBMITTED NOA A JOHN MANSVILLE PRODUCT
 WHICH WAS STAMPED AND REVIEWED BY THE DESIGNER OF
 RECORD. PLEASE REVISE SO THE SPECS AND SUBMITTALS WILL
 COINCIDE. PLEASE CIRCLE THE SUBSYSTEM TO BE INSTALLED
 IN THE PRODUCT APPROVAL, REVIEW THE PRESSURES THE
 SYSTEM IS LISTED FOR , IT MAY REQUIRE ENHANCED
 FASTENING SEE SYSTEMS LIMITATION EITHER 7 OR 9 FOR A
 MIAMI-DADE NOA.
  
 13A) A-105 VERSES THE INPUT DATA REPORT FROM THE ENERGY
 CALCULATIONS, WALLS, IN THE INPUT DATA REPORT ALL WALLS
 ARE DESIGNED AS BLOCK WALLS PLEASE NOTE THE FUTURE
 TENANT BUILD-OUT IS A METAL STUD WALL PLEASE CORRECT.
 THE OTHER ISSUE IS THE ENERGY INPUT REPORT ALSO
 INDICATES THE USE OF ?? ISO BOARD AND INSTALLATION OF
 5/8? GYPSUM PLEASE SEE DETAIL# 2 AND INSULATION NOTE#1
 FOR BLOCK AND METAL STUD.
  
 13B)A-105DETAIL# 2 THE WALL INSULATION DOES NOT
 CONTINUE TO THE LOCATION WHERE THE ROOFING INSULATION
 WILL BE REQUIRED (BENEATH THE ROOF DECK) WALL
 INSULATION SHALL BE CONTINOUSOUS13-400 APPENDIX B
 2.2.1.1.
  
 13C) A-105 DETAIL# 2 HAS A NOTE S.S. NOTE# 1, THIS NOTE
 INDICATES A SYNTHETIC STUCCO SYSTEM STO OR EQUAL.
 INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 14) SHEET A-107 KITCHEN W/ HC SINK. PLANS INDICATE WHAT
 APPEARS TO BE DOORS AND A BOTTOM SHELF. 11-4.24.5 CLEAR
 FLOOR SPACE. A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY
 48 INCHES (760 MM BY 1219 MM) COMPLYING WITH SECTION
 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK.
  
 15) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 AND
 1609.6.2.2 COMPONENTS AND CLADDING WILL REQUIRE PRODUCT
 APPROVALS, MISSING PRODUCT APPROVALS ARE:
 15A) WALL LOUVERS RULE 9B-72 (31)?
 15B) EFIS WALL AND SOFFIT SYSTEMS RULE 9B(31)?
 15C) ROOF FLAT DECK RULE 9B72(31)( D) WRONG REPORT
 SUBMITTED FOR STRUCTURAL CONCRETE AND
 PLANK DECKS SHEET S-2.0 INDICATES METAL DECK WITH LIGHT
 WEIGHT CONCRETE.
 16) MONIER ROOF TILE CIRCLE THE METHOD OF ATTACHMENT.
 1609.6.2.2./ 1715.2.1.
  
 17) PLEASE SUBMIT INFORMATION ON HOW THE RIDGE TILE ARE
 GOING TO BE SECURED TO THE ROOFING SYSTEM. 1507.3.7
 ATTACHMENT. CLAY AND CONCRETE ROOF TILES SHALL BE
 FASTENED IN ACCORDANCE WITH SECTION 1609 OR IN
 ACCORDANCE WITH FRSA/RTI INSTALLATION MANUAL.
 1507.3.8 APPLICATION. TILE SHALL BE APPLIED ACCORDING
 TO THE MANUFACTURER?S INSTALLATION INSTRUCTIONS OR
 RECOMMENDATIONS OF THE FRSA/RTI 07320- 04.
  
  
 18) SHEET S-0.1 THE PLANS INDICATE THE WIND INFORMATION
 DESIGNED TO ASCE 7-05. 2004 FBC 1609.1.1 & CHAPTER 35
 REFERENCED STANDARDS RECOGNIZES ASCE 7-02 . ALSO
 1603.1.4 WIND DESIGN DATA. PLEASE CORRECT.
  
 19) SHEET S-0.1 NOTE F-2 REFERENCES THE RESIDENTIAL
 CODE WITH SECTION R1816, PLEASE UPDATE.
  
 20) SHEET S-0.1 VENTILATION NOTE# 1 REFERENCES THE
 SOUTH FLORIDA BUILDING CODE WITH NO VENTILATION
 REQUIRED. PLEASE REVIEW SECTION 1203.2 FOR EAVE VENTS
 AS WELL AS VENTS REQUIRED AT LEAST 3 FEET ABOVE THE
 EAVE OR CORNICE VENTS. COMMENTARY ADDRESSES EXCEPTION
 IF ROOF SPACES ARE NOT CREATED(E.G., SOLID CONCRETE
 ROOF SECTIONS), VENTILATION IS NOT REQUIRED.
  
 21) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  