Plan Review Notes For Permit 08110559 |
Permit Number |
08110559 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-11-26 13:28:18 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | ARE USED, COMPLETE THE ATTACHED INSTALLATION SCHEDULE. | | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 507.3, | | PROVIDE CALCULATIONS. THERE IS A STATEMENT ON THE NOA | | THAT SHUTTERS ARE EXISTING. PLEASE PROVIDE A PERMIT | | NUMBER FOR THE EXISTING SHUTTERS. | | | | 2. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. | | NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING | | SIZE FOR BEDROOMS, FBC R310, FBC EB 505.1. | | | | |
|