2008-12-10 16:57:20 | RESIDENTIAL (R3) ROOF FRAMING, BUILDING REVIEW |
| CHECKLIST. |
| REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| REVISIONS. |
| |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| NOTE: THIS MAY BE SUBMITTED AT TIME OF PERMIT PICK UP. |
| |
| 2- SHEET 2: |
| A) PROVIDE CONNECTION DETAIL AT POINT WHERE THE TWO HIP |
| RAFTERS MEET THE ROOF GIRDER. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH THE |
| DESIGN LOADS OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL |
| CODE. THERE IS NOT DETAIL OR SPECS PROVIDED FOR THIS |
| CONNECTION. |
| |
| B) CLARIFY IF ROOF IS GOING TO BE ATTACHED TO EXISTING |
| HOUSE OR NOT. PROVIDE DETAIL AS REQUIRED. SEC. 106.1.2 |
| CITY AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH |
| THE DESIGN LOADS OF SEC. R301 OF 2004 FLORIDA |
| RESIDENTIAL CODE. |
| |
| C) CLARIFY IF HIP ROOF RAFTER IS A 2X MEMBER OR 4X |
| MEMBER. CONNECTOR "B" SPECIFIED ON CONNECTOR SCHEDULE |
| IS HCP4Z, WHICH IS FOR A 4X WOOD MEMBER. ROOF FRAMING |
| PLAN SHOWS A 2X WOOD MEMBER. REVISE/CLARIFY AS |
| REQUIRED. |
| |
| D) SPECIFY CONNECTION OF ROOF RAFTERS TO HIP RAFTER. |
| THERE IS NOT CONNECTOR SPECIFIED ON ROOF FRAMING PLAN. |
| SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO VERIFY |
| COMPLIANCE WITH SEC. R301 OF 2004 FLORIDA RESIDENTIAL |
| CODE. |
| |
| 3- SHEET 3: |
| A) REVISE ROOF SHEATHING NAILING SCHEDULE TABLE AND |
| PLYWOOD NAILING SKETCH. NAIL TYPE TO BE 8D RING SHANK |
| NAILS (NOT PLAIN 8D) FOR ALL ROOF ZONES. ALSO, ROOF |
| ZONE 3 NEEDS TO HAVE NAIL SPACING AT 4"O.C. AT EDGES |
| AND INTERMEDIATE SUPPORTS AS REQUIRED BY SEC. |
| R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. REVISE AS |
| REQUIRED. |
| ALSO, REMOVE NOTE STATING THAT RING SHANK NAILS ARE NOT |
| REQUIRED WHEN MEAN ROOF HEIGHT <25'. |
| |
| B) WIND ZONES SKETCH SHOWING THE HIP ROOF ON ONE SIDE |
| AND GABLE END ON THE OTHER SIDE IS MISSING ROOF ZONES 2 |
| AND 3 ON HIP SIDE. REVISE AS REQUIRED. SEE FIGURE |
| R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| C) TYPICAL WALL SECTION SHOWS 1X6 FASCIA BOARD, WHILE |
| PLYWOOD NAILING DETAIL SHOWS 2X6 WOOD FASCIA. REVISE AS |
| REQUIRED TO MATCH. |
| |
| 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| DCA RULE 9B-72 FOR ALL SIMPSON STRUCTURAL CONNECTORS |
| SPECIFIED ON PLANS AND DETAILS. |
| NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER |
| PAGE AND PAGE WHERE CONNECTOR IS SHOWN. NO NEED TO |
| SUBMIT COMPLETE REPORT. THIS APPLIES TO STRUCTURAL |
| CONNECTORS ONLY. |
| |