Plan Review Notes For Permit 08110518 |
Permit Number |
08110518 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-03-04 10:37:42 | ***DENIED*** | | | | 1) OK | | | | 2) OK | | | | 3) THE PLANS ILLUSTRATE THE DISTANCE FROM THE CLOSEST | | FIRE HYDRANT. THE PREVIOUS COMMENT REQUESTED THE HOSE | | LAY DIATNCE FROM A FIRE APPARATUS. PLEASE NOTE THAT IF | | THE DISTANCE EXCEEDS 150' A CLASS I STANDPIPE SYSTEM IS | | REQUIRED IN ACCORDANCE WITH NFPA 303, SEC. 4.4.1. IF | | THIS PROJECT REQUIRES A STANDPIPE SYSTEM, PROVIDE THE | | FIRE PROTECTION DRAWINGS AND DETAILS. | | | | 4) OK | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|