Plan Review Notes
Plan Review Notes For Permit 08110518
Permit Number 08110518
Review Stop B
Sequence Number 2
Notes
Date Text
2009-03-09 15:19:31BUILDING PLAN REVIEW
 PERMIT: 08110518
 ADD: 2400 N FLAGLER
 CONT: PLAN REVIEW
 TEL: (561)248-5574/ CARL SHEPARD
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 MARCH 09/09
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) BOAT ADA LIFT REMOVED FROM SHEET 1 THROUGH 7. ADA
 TRANSFER OR BOAT LIFT, PLEASE PROVIDE INFORMATION
 .TITLE III OF THE ADA PUBLIC TRANSPORTATION SYSTEMS AND
 TITLE II PUBLIC FACILITY.
  
 6) SEMI-COMPLIED. PLANS NOW SHOW A GUARD RAIL ON THE
 SIDES OF THE FLOATING DOCK WHERE BOATS ARE NOT LOADING.
 THE PROBLEM IS THE 1012.3 OPENING LIMITATIONS, THE
 GUARD IS TO BE ABLE TO REJECT A 4" SPHERE, THE PLANS
 FOR BOTH THE FLOATING DOCK AND GANGWAY DO NOT INDICATE
 THIS.
  
 7) 2ND REQUEST, SHEET 6 INDICATES THE USE OF HURRICANE
 STRAPS OR TIES, RULE 9-B REQUIRES PRODUCT APPROVALS FOR
 SUCH ITEMS, RULE 9-B(31)(G).
 106.3 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 8) NOT TO BE ENFORCED BY RULE OF NEW B.O.
  
 9) ELECTRICAL SHEET# 4 INDICATES THE USE OF LIGHT POLES
 BUT AGAIN THERE IS NO DESIGN CRITERIA FOR WIND,
 1603.1.4.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  