2008-12-09 15:33:58 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} INCLUDE THE ADDRESS OF THE PROJECT ON THE PLANS PER |
| 106.1.1 FBC AS AMENDED. |
| |
| 2} 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE |
| PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL (SEE ALSO SECTION |
| 106.3.5).THERE IS NOT ENOUGH INFORMATION ON THE PLAN TO |
| REVIEW ELECTRICAL EQUIPMENT, SYSTEM, INSTALLATION ETC. |
| ALSO SEE ARTICLE 555 NEC, 2005, NFPA-303-2000 CHAPTER |
| 3. |
| |
| 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| FS, RESPECTIVELY. |
| THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, |
| IF EXEMPTIONS APPLY.SEE PAGES 8 & 9. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |