Plan Review Notes
Plan Review Notes For Permit 08110461
Permit Number 08110461
Review Stop B
Sequence Number 4
Notes
Date Text
2009-03-16 11:09:33BUILDING PLAN REVIEW
 PERMIT: 08110461/06111071
 ADD: 2455 METROCENTRE BLVD
 CONT: CROWTHERS ROOFING
 TEL: (954)536-3959
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 HOMEWOOD SUITES HOTEL/ HILTON
 FIVE STORY/ 114 UNITS
  
 MARCH 16,2009
 ROOF REVISION REVIEW: REVISION# 1
  
 ACTION: DENIED
  
 1) TSE REPORTOR JOB NO. 8085.16 DOES NOT STATE THE WIND
 DESIGN CRITERIA NOR DO WE HAVE A SK-1 BY NIELSEN
 -HARRELL IN THIS ROOFING PACKAGE NOR THE ISSUED SET OF
 PLANS FOR THIS PERMIT.
 WE DO HAVE DOCUMENTS FROM TSE DATED OCT.24TH, 2008
 PROVIDING THE WIND DESIGN FOR THE FLAT ROOF PORTION OF
 THE PROJECT. SINCE THIS IS A REVISION PLEASE PROVIDE
 THE WIND DESIGN CRITERIA FOR THIS PORTION OF THE
 PROJECT. ASCE 7-02 SECTION 6.
  
 2) THE SECOND ISSUE IS THE PRODUCT APPROVAL SUBMITTED
 FOR THE CROWTHER METAL ROOFING (FL 4975) DOES NOT HAVE
 ANY OF THE REPORT AND RECOMMENDED DETAILS,
 SPECIFICATIONS AND TRIM, I'VE PRINTED OUT ONE SET,
 THREE ARE REQUIRED FORTHE THRESHOLD BUILDING.109.3.6
 PERATING GUIDELINES FOR THRESHOLD INSPECTORS (3 COPIES
 OF ALL PRODUCT APPROVALS).
  
 3) THERE IS A DISCREPANCY BETWEEN THE FLORIDA PRODUCT
 APPROVAL SUBMITTED( FL 4975) AND THE TSE REPORT DATED
 FEB.21, 2009 THIS REPORT LIST ON PAGE 2 OF 3 SEE FL
 PRODUCT APPROVAL
 (11797) THERE IS NO SUCH REPORT UNDER THE 2004 FLORIDA
 APPROVAL SYSTEM? 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 NOTATION OF FLAT DECK APPROVED UNDER PERMIT ISSUANCE.
 FLAT DECK: NOA: 05-0803.04
 FIRESTONE TPO SINGLE PLY ROOF SYSTEMS OVER LIGHTWEIGHT
 CONRETE DECK
 PAGE 6 OF 9
 MEMBRANE TYPE: SINGLE PLY, TPO REINFORCED
 DECK TYPE 41: LIGHTWEIGHT CONCRETE, INSULATED
 DECK DESCRIPTION CELLULAR LIGHTWEIGHT CONCRETE
 SYSTEM TYPE A(2) MEMBRABE FULLY ADHERED
 MAXIMUM DESIGN PRESSURE -135, LIMITATION# 7
  
 NOTE TO MEET THE ENERGY CALCS AT ROOF DRAINS 1 INCH
 INSULATION WITH A MINIMUM OF 2" LIGHTWEIGHT CONCRETE.
 PLEASE REVIEW INSULATION BOARD LAYOUT SHEET UNDER THE
 ROOFING PERMIT FOR TAPERED ROOF INSULATION.
  
  
  
 @004 FBC-4975
 CROWTHER ROOFING & SHEET METAL
 4975.2 MECHANICAL LOCK
 UPLIFT: +/-105
  