2008-11-25 15:01:52 | BUILDING PLAN REVIEW |
| PERMIT: 08110461 |
| ADD: 2455 METROCENTRE BLVD |
| CONT: CROWTHER ROOFING |
| TEL: (239)337-1300 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| HOMEWOOD SUITES |
| ACTION: DENIED |
| |
| 1) SHEET LWC LAYOUT SHEET INDICATES THAT AT THE ROOF |
| DRAINS THERE IS NO INSULATION ONLY THE LIGHT WEIGHT |
| CONCRETE THEN THE INSULATION BOARD IS STAGERED IN |
| HEIGHT 1" THROUGH 7". PLEASE REVIEW THE ENERGY |
| CALCULATIONS REQUIRING A MINIMUM OF 6" AT THE ROOF |
| DRAIN. THE DATA INPUT REPORT INDICATES A MINIMUM OF 6" |
| INSULATION WITH 3" LIGHT WEIGHT CONCRETE ON TOP. PLEASE |
| SEE 13-404.1.A THE MINIMUM PERFORMANCE LEVEL OF |
| INSULATION IS JUST THAT IT IS NOT AN AVERAGE BUT THE |
| MINIMUM AMOUNT REQUIRED. |
| |
| THE PRODUCT HOL-E-BOARD R-VALUES ONLY GO TO 5" PLEASE |
| PROVIDE FOR THE THICKER REQUIREMENTS REQUIRED FOR THIS |
| JOB. |
| |
| CONCERNS ARE WITH THE AMOUNT OF INSULATION REQUIRED, |
| WILL THERE BE FASTENERS ON THE MARKET TO SECURE THE |
| PRODUCT IN QUESTION OR WILL THERE NEED TO BE MORE ROOF |
| DRAINS CLOSER TOGETHER TO REDUCE THE AMOUNT OF MATERIAL |
| IT WILL TAKE TO HAVE A COMPLIANT ROOF. |
| |
| 2) TITEN STRUCTURAL ENGINEERING ENHANCED FASTENING |
| DOCUMENT WILL NEED TO BE ORIGINAL SIGNATURE AND SEAL |
| NOT COPIES. PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING |
| FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE |
| DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS |
| PLEASE NOTE THE TSE REPORT SUBMITTED REFRENECES JOHN |
| MANSVILLE PERMA PLY 28 (NOA 06-0626.05) BASE SHEET |
| FASTENER PATTERNS FOR ZONES 2 & 3 BUT THE REPORT WAS |
| NOT SUBMITTED. |
| REPORTS SUBMITTED: |
| |
| NOA 07-0228.07 JOHN MANSFIELD MOD BIT OVER LIGHTWEIGHT |
| CONCRETE DECK |
| |
| NOA 05-0803.04 TPO SINGLE PLY OVER LIGHTWEIGHT CONCRETE |
| DECK |
| |
| NOA 03-0923.03 EXPIRED 10-19-08 CELCORE LIGHTWEIGHT |
| INSULATING CONCRETE |
| ------------------------------------------------------- |
| -------- |
| NOA 07-1023.09 SPANISH "S" ROOF TILE |
| |
| NOA 04-1116.01 POLYSET ONE ROOF TILE ADHESIVE |
| |
| NOA 07-0124.02 DENS DECK |
| |
| FL 8380.1DCSM STEEL RIDGE ANCHOR |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |