2008-11-25 15:01:52BUILDING PLAN REVIEW
 PERMIT: 08110461
 ADD: 2455 METROCENTRE BLVD
 CONT: CROWTHER ROOFING
 TEL: (239)337-1300
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 HOMEWOOD SUITES
 ACTION: DENIED
  
 1) SHEET LWC LAYOUT SHEET INDICATES THAT AT THE ROOF
 DRAINS THERE IS NO INSULATION ONLY THE LIGHT WEIGHT
 CONCRETE THEN THE INSULATION BOARD IS STAGERED IN
 HEIGHT 1" THROUGH 7". PLEASE REVIEW THE ENERGY
 CALCULATIONS REQUIRING A MINIMUM OF 6" AT THE ROOF
 DRAIN. THE DATA INPUT REPORT INDICATES A MINIMUM OF 6"
 INSULATION WITH 3" LIGHT WEIGHT CONCRETE ON TOP. PLEASE
 SEE 13-404.1.A THE MINIMUM PERFORMANCE LEVEL OF
 INSULATION IS JUST THAT IT IS NOT AN AVERAGE BUT THE
 MINIMUM AMOUNT REQUIRED.
  
 THE PRODUCT HOL-E-BOARD R-VALUES ONLY GO TO 5" PLEASE
 PROVIDE FOR THE THICKER REQUIREMENTS REQUIRED FOR THIS
 JOB.
  
 CONCERNS ARE WITH THE AMOUNT OF INSULATION REQUIRED,
 WILL THERE BE FASTENERS ON THE MARKET TO SECURE THE
 PRODUCT IN QUESTION OR WILL THERE NEED TO BE MORE ROOF
 DRAINS CLOSER TOGETHER TO REDUCE THE AMOUNT OF MATERIAL
 IT WILL TAKE TO HAVE A COMPLIANT ROOF.
  
 2) TITEN STRUCTURAL ENGINEERING ENHANCED FASTENING
 DOCUMENT WILL NEED TO BE ORIGINAL SIGNATURE AND SEAL
 NOT COPIES. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G15-23.002 ENGINEERS
 PLEASE NOTE THE TSE REPORT SUBMITTED REFRENECES JOHN
 MANSVILLE PERMA PLY 28 (NOA 06-0626.05) BASE SHEET
 FASTENER PATTERNS FOR ZONES 2 & 3 BUT THE REPORT WAS
 NOT SUBMITTED.
 REPORTS SUBMITTED:
  
 NOA 07-0228.07 JOHN MANSFIELD MOD BIT OVER LIGHTWEIGHT
 CONCRETE DECK
  
 NOA 05-0803.04 TPO SINGLE PLY OVER LIGHTWEIGHT CONCRETE
 DECK
  
 NOA 03-0923.03 EXPIRED 10-19-08 CELCORE LIGHTWEIGHT
 INSULATING CONCRETE
 -------------------------------------------------------
 --------
 NOA 07-1023.09 SPANISH "S" ROOF TILE
  
 NOA 04-1116.01 POLYSET ONE ROOF TILE ADHESIVE
  
 NOA 07-0124.02 DENS DECK
  
 FL 8380.1DCSM STEEL RIDGE ANCHOR
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved