2008-11-26 16:12:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. SEE FBC1002, DEFINITION OF COMMON PATH OF TRAVEL.
 THE LIFE SAFETY PLAN A0.03 SHOWS THE TRAVEL DISTANCE
 FROM THE FARTHEST POINT TO THE CORRIDOR ENTRANCE. THIS
 SHOULD BE MEASURED TO THE POINT AT WHICH THERE ARE TWO
 SEPARATE AND DISTINCT PATHS OF EGRESS TRAVEL TO TWO
 EXITS. THIS IS NOT TO EXCEED 100', FBC1013.3.
  
 2. EXIT ACCESS TRAVEL DISTANCE IS TO BE MEASURED ALONG
 THE NATURAL AND UNOBSTRUCTED PATH OF EGRESS TRAVEL
 FBC1015.1. THIS WILL MOST LIKELY BE ALONG WALLS DUE TO
 PARTITION WALLS AND FURNITURE PLACEMENT, NOT ACROSS THE
 DIAGONAL OF THE BUILDING AS SHOWN. PLEASE REVISE PATH
 AND TRAVEL DISTANCE.
  
 3. THIS PERMIT WILL BE ISSUED AT RISK, BASED ON AN
 ANTICIPATED POSSIBLE FLOOR PLAN. COMPLIANCE WITH TRAVEL
 DISTANCE, COMMON PATH, ETC. WILL BE SHOWN ON THE TENANT
 BUILDOUT PERMITS.