Plan Review Notes
Plan Review Notes For Permit 08110405
Permit Number 08110405
Review Stop E
Sequence Number 4
Notes
Date Text
2010-03-17 15:33:00ELECTRICAL REVIEW COMMENTS:
  
 1. NOTE: REVIEW WAS DONE UNDER THE 2008 NEC. IF UNDER
 THE 2005 NEC PLEASE DISREGARD AREA COMMENTS NOTED WITH
 2008 NEC.
  
 2. NOTE: THERE IS CONFUSION OVER THE SERVICE AS SHOWN.
 THE ELECTRICAL RISER STATES *EXISTING ELECTRICAL RISER
 DIAGRAM*. HOWEVER, THERE ARE SEVERAL ITEMS WHICH ARE
 ALSO SHOWN AS NEW. REVIEW IS BASED ON THESE ITEMS AS
 NEW AND NOT EXISTING. THERE IS INFORMATION NOT YET
 SHOWN TO CONFIRM A COMPLETE REVIEW.
 A) PLEASE SEE 250.94 FOR REQUIRED INTERSYSTEM BOND.
 2008 NEC.
 B) PLEASE INDICATE THE SIZE OF THE EXISTING SERVICE TO
 INCLUDE SERVICE ENTRANCE CONDUCTORS. 240.4, 31.16,
 310.15 ETC.
 C) PLEASE COORDINATE PANELS AND RISER. PANELS ARE SHOWN
 RATED AT 150AMPS, YET THE RISER INDICATES PANELS AS
 100AMPS.
 D) PLEASE SEE RISER AS BOTH DISCONNECTS SHOWN FOR BOTH
 UPSTAIRS AND DOWNSTAIRS PANELS ARE RATED AT 200AMPS. IT
 IS NOT PERMITTED TO HAVE 200AMP RATED OVER CURRENT
 PROTECTION FEEDING 100AMP OR 150AMP RATED PANELS.
 E) THE SAME 200AMP RATED DISCONNECTS ARE SHOWN ON
 FEEDERS RATED FOR 100AMPS. THIS IS NOT PERMITTED.
 PLEASE VERIFY MAINS AND OVERCURRENT PROTECTION. 310.16,
 240.4, 310.15B6
  
 3. NOTE: PLEASE SEE 210.12 OF THE 2008 NEC AND LIST ALL
 REQUIRED ARC FAULT PROTECTED CIRCUITS. PLEASE SEE SAME
 CODE SECTION UNDER THE 2005 NEC AND LIST ACCORDINGLY.
  
 4. NOTE: PLEASE SEE 406.8 FOR REQUIRED RECEPTACLES
 OUTSIDE IN DAMP OR WET LOCATIONS. 2008 NEC
  
 5. NOTE: PLEASE SEE 250.32, 250.66, 250.50 FOR
 GROUNDING ELECTRODE SYSTEM REQUIRED AT DETACHED
 BUILDING.
  
 6. NOTE: PLEASE SEE 250.66 FOR SIZING OF THE GROUNDING
 ELECTRODE CONDUCTOR AT SERVICE. AS THE SERVICE ENTRANCE
 CONDUCTORS AND THE SIZE OF SERVICE ARE NOT SHOWN, THE
 #4 AS SHOWN CANNOT BE CONFIRMED TO BE CODE COMPLIANT.
 BASED ON THE LOAD AND SIZE OF ALL OVER CURRENT
 PROTECTIVE DEVICES SHOWN, THE GROUNDING ELECTRODE IS
 TOO SMALL.
  
 7. NOTE: CLOSET LIGHT FIXTURES SHOWN DO NOT APPEAR TO
 MEET 410.8
  
 8. NOTE: PLANS DO NOT CONTAIN ANY DESIGN PROFESSIONAL
 MEETING 481, 471, 489 OR 481.229, 471.003 EXCEPTIONS
 PLEASE BE SURE PLANS CONTAIN RESPONSIBLE DESIGNER UNDER
 SECTIONS NOTED.
  
 9. NOTE: ALL RECEPTACLES SERVING KITCHEN COUNTER SPACE
 ARE REQUIRED TO BE GFI/GFI PROTECTED. 210.8A6
  
 10. NOTE: OVER CURRENT PROTECTION FOR 5KW AHU IS TOO
 HIGH. 422.11
  
 11. NOTE: LIGHTING FIXTURE REQUIRED IN KITCHEN AND ALSO
 SHOWS LIGHT SWITCH NOT CONTROLLING ANYTHING? 210.70
 NEW OR EXISTING LIGHT FIXTURES IN STAIRS?
 NEW OR EXISTING LIGHT IN SECOND FLOOR BATH?
  
 12. NOTE: MISSING SMOKE ALARM PER 11.5.1, 11.8.3 OF
 NFPA-72 ON LOWER LEVEL OF STAIRS LEADING TO FLOOR
 ABOVE.
  
 13. NOTE: PANEL SCHEDULES NEED TO BE SPECIFIC. FIRST
 FLOOR ONLY INDICATES ONE CIRCUIT FOR GENERAL LIGHTING.
 WHERE ARE THE OTHER GENERAL LIGHTING AND RECEPTACLE
 CIRCUITS? THESE ARE ALSO REQUIRED TO BE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. THE USE OF GENERAL
 LIGHTING AND RECEPTACLES IS NO LONGER ACCEPTACLE UNDER
 THE 2005 AND 2008 NEC. 408.4
  
 14. NOTE: NO ELECTRICAL SHOWN ON PLANS FOR SECOND FLOOR
 WASHER/DRYER? FBC 106.3.5.1.2, 210.52F, 210.11C2
  
 15. NOTE: DISCONNECTS FOR PANELS AT DETACHED STRUCTURE
 ARE SHOWN ON PLANS, HOWEVER NOT ON RISER. 225.31-225.39
  
  
 DEWEY PALMER
  