2009-02-18 12:51:58 | |
| APPLICATION #08110405 ELECTRICAL PLAN REVIEW |
| 716 NEW YORK STREET 1/8/09 |
| WEST PALM BEACH, FL. |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| NEC, NFPA-72 2002, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| ALL COMMENTS RELATE TO SHEET 7.1, UNLESS OTHERWISE |
| NOTED |
| |
| THESE COMMENTS FROM THE PREVIOUS REVIEW NEED FURTHER |
| RESPONCE, INDICATED BY *** |
| |
| 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| FS, RESPECTIVELY*** NOT DONE AND NO RESPONSE GIVEN. |
| |
| 3} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL |
| SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLES 230 |
| AND 225 CAN BE REVIEWED*** THE SITE PLAN SHOWS THERE |
| ARE NO DISCONNECTS ON THE BACK BUILDING PER |
| 230.70(A)(1) "READILY ACCESSIBLE LOCATION THE SERVICE |
| DISCONNECTING MEANS SHALL BE INSTALLED AT A READILY |
| ACCESSIBLE LOCATION EITHER OUTSIDE OF A BUILDING OR |
| STRUCTURE OR INSIDE NEAREST THE POINT OF ENTRANCE OF |
| THE SERVICE CONDUCTORS". ALSO SEE 250.32 FOR GROUNDING |
| OF SEPARATE STRUCTURES. INCLUDE ON THE RISER. |
| |
| 7 } PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE |
| FEEDERS ON THE RISER DIAGRAM.***THIS COMMENT MUST BE |
| RESPONDED TOO SO THE COMPLIANCE FOR 250.122, |
| 310.15(B)(6) CAN BE REVIEWED. THE RESPONSE OF THE |
| SERVICE BEING INSTALLED UNDER ANOTHER PERMIT IS ONLY |
| PARTIALLY CORRECT AS THAT PERMIT (#06120063) EXPIRED |
| WITHOUT HAVING PASSED ANY INSPECTIONS. THE CONDUCTORS |
| AND CONDUIT SIZE AND TYPE NEED TO BE VERIFIED AS |
| COMPLIANT. INDICATE ON DRAWINGS. |
| |
| PLEASE REMOVE OLD SHEETS, INSERT NEW ONES, SUBMIT OLD |
| SHEETS (ONE SET) TO EXPEDITE REVIEW AND SUBMIT WRITTEN |
| RESPONSE TO THE COMMENTS MADE IN THIS REVIEW. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| [email protected] |
| |