Plan Review Notes
Plan Review Notes For Permit 08110405
Permit Number 08110405
Review Stop E
Sequence Number 1
Notes
Date Text
2009-01-08 16:31:35 
  
 APPLICATION #08110405 ELECTRICAL PLAN REVIEW
 716 NEW YORK STREET 1/8/09
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET 7.1, UNLESS OTHERWISE
 NOTED
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
  
 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 3} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL
 SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLES 230
 AND 225 CAN BE REVIEWED.
  
 4} PROVIDE LOAD CALCULATIONS FOR THE SERVICE SHOWN
 (INCLUDING THE MAIN HOUSE) PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED.
  
 5} THERE ARE TWO RECTANGULAR BOXES IN THE FEED FROM THE
 PANEL TO THE 100 AMP PANELS IN THE BACK BUILDING.
 INDICATE IF THESE ARE EQUIPMENT, AND IF SO WHAT. ADD TO
 ELECTRICAL SYMBOLS LEGEND ALONG WITH AN EXPLANATORY
 NOTE. 215.5 NEC
  
 6} LOCATE ALL PANELS AND DISCONNECTS ON THE FLOOR PLAN
 FOR THE UNITS, THIS SHEET. 215.5 NEC.
  
 7 } PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE
 FEEDERS ON THE RISER DIAGRAM.
  
 8} THE A/C IS LISTED AS 5 KW IN THE LOAD CALCULATIONS
 BUT SHOWN AS 10 KW IN THE PANEL SCHEDULES, BOTH FLOORS.
 THERE ARE NO MANUFACTURES SPECIFICATIONS FOR THE AIR
 HANDLERS ON SHEET 6.1, PROVIDE SAME SO THE CORRECT
 CALCULATIONS AND PANEL SCHEDULE OCP AND CONDUCTOR SIZES
 MAY BE REVIEWED. 220, 240 NEC. SEE NOTE 16 THIS SHEET.
  
 9} THE BATH CIRCUITS REQUIRED BY 210.11(C)(3) ARE NOT
 LISTED ON THE PANEL SCHEDULE.
  
 10} THERE ARE DISHWASHERS ON THE PANEL SCHEDULES (BOTH)
 THAT ARE NOT SHOWN IN THE UNITS OR LISTED IN THE
 CALCULATIONS. 408.4 NEC.
  
 11} THERE ARE NO SMOKE ALARMS IN THE FIRST FLOOR UNIT.
 313.1.1
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER