| APPLICATION #08110405 ELECTRICAL PLAN REVIEW |
| 716 NEW YORK STREET 1/8/09 |
| WEST PALM BEACH, FL. |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| NEC, NFPA-72 2002, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| ALL COMMENTS RELATE TO SHEET 7.1, UNLESS OTHERWISE |
| NOTED |
| |
| 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| FS, RESPECTIVELY. |
| |
| 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| |
| 3} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL |
| SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLES 230 |
| AND 225 CAN BE REVIEWED. |
| |
| 4} PROVIDE LOAD CALCULATIONS FOR THE SERVICE SHOWN |
| (INCLUDING THE MAIN HOUSE) PER ARTICLE 220 PART III, |
| STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. |
| |
| 5} THERE ARE TWO RECTANGULAR BOXES IN THE FEED FROM THE |
| PANEL TO THE 100 AMP PANELS IN THE BACK BUILDING. |
| INDICATE IF THESE ARE EQUIPMENT, AND IF SO WHAT. ADD TO |
| ELECTRICAL SYMBOLS LEGEND ALONG WITH AN EXPLANATORY |
| NOTE. 215.5 NEC |
| |
| 6} LOCATE ALL PANELS AND DISCONNECTS ON THE FLOOR PLAN |
| FOR THE UNITS, THIS SHEET. 215.5 NEC. |
| |
| 7 } PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE |
| FEEDERS ON THE RISER DIAGRAM. |
| |
| 8} THE A/C IS LISTED AS 5 KW IN THE LOAD CALCULATIONS |
| BUT SHOWN AS 10 KW IN THE PANEL SCHEDULES, BOTH FLOORS. |
| THERE ARE NO MANUFACTURES SPECIFICATIONS FOR THE AIR |
| HANDLERS ON SHEET 6.1, PROVIDE SAME SO THE CORRECT |
| CALCULATIONS AND PANEL SCHEDULE OCP AND CONDUCTOR SIZES |
| MAY BE REVIEWED. 220, 240 NEC. SEE NOTE 16 THIS SHEET. |
| |
| 9} THE BATH CIRCUITS REQUIRED BY 210.11(C)(3) ARE NOT |
| LISTED ON THE PANEL SCHEDULE. |
| |
| 10} THERE ARE DISHWASHERS ON THE PANEL SCHEDULES (BOTH) |
| THAT ARE NOT SHOWN IN THE UNITS OR LISTED IN THE |
| CALCULATIONS. 408.4 NEC. |
| |
| 11} THERE ARE NO SMOKE ALARMS IN THE FIRST FLOOR UNIT. |
| 313.1.1 |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |