2009-01-14 13:26:24RESIDENTIAL (R3) ADDITION/ALTERATION/RENOVATION
 BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS DOCUMENT MAY BE RECORDED LATER AT TIME OF
 PERMIT PICK UP.
  
 2- SHEET 1.1:
 A) CLARIFY SCOPE OF WORK. PERMIT APPLICATION DESCRIBES
 REMODELING THE INTERIOR AND EXTERIOR ACCORDING TO
 PLANS. PERMIT APPLICATION DOESN'T INCLUDE THE ADDITION
 OF THE NEW BALCONY. ALSO, IS NOT CLEAR IF AREA OF WORK
 IS THE REAR ACCESSORY BUILDING ONLY. OR IF EXISTING
 MAIN HOUSE IS GOING TO HAVE SOME WORK ALSO. THERE IS
 ONLY ONE NOTE ON MAIN HOUSE SAYING THAT EXISTING
 RESIDENCE TO BE REMODELED, BUT THE DRAWINGS DON'T SHOW
 ANY WORK FOR THE MAIN HOUSE. FENCES AND PRIVACY WALL
 ARE TO BE DONE UNDER SEPARATE PERMITS. CLARIFY NOTES
 REGARDING GRADING SLOPE. IS REGRADING PART OF THE SCOPE
 OF WORK IN THIS PERMIT?
  
 ***NOTE: SEE COMMENTS ON REVIEWED SET OF PLANS AND
 RETURN REVIEWED SET AFTER COMMENTS ARE ADDRESSED ON
 ORIGINAL PLANS TO EXPEDITE THE REVIEW PROCESS.
  
 3- SHEET 2.1: CLARIFY SCOPE OF WORK FOR GUEST HOUSE
 NOTE: EXPAND BUILDING +/- 1'-6" TO ACCOMMODATE STAIRS
 TO MEET CURRENT CODE. THERE IS NOT INFORMATION PROVIDED
 TO SHOW COMPLIANCE WITH THIS NOTE. AND, PLANS DON'T
 SHOW ANY BUILDING EXPANSION. ON THE OTHER HAND CHECK
 ZONING COMMENTS REGARDING BUILDING EXPANSION.
  
 4- SHEET 3.1:
 A) SPECIFY SAFETY GLASS FOR WINDOWS ON BATHROOMS AS
 REQUIRED BY SEC. R308.4 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 B) CLARIFY SCOPE OF WORK FOR GUEST HOUSE REGARDING THE
 EXPANSION OF BUILDING +/- 1'-6" TO ACCOMMODATE STAIRS.
 THERE IS NOT INFORMATION ON PLANS REGARDING THIS ISSUE.
  
 C) CLARIFY FLOOR FRAMING NOTE. THERE IS NOT SECTION #1
 ON SHEET 6.1. ALSO, CLARIFY SCOPE OF WORK TO BE
 PERFORMED. COORDINATE WITH ITEM 2A ABOVE.
  
 D) NEW BALCONY FRAMING PLAN:
 *SPECIFY ALL BEAMS. CLARIFY WHY SHOWING ONLY ONE MEMBER
 TO RECEIVE ALL FLOOR JOISTS?.
  
 **CLARIFY IF USING 2X6 FLOOR JOISTS OR 2X8 FLOOR
 JOISTS. BOTH ARE MENTIONED ON PLAN. SEE COMMENTS ON
 REVIEWED SET OF PLANS.
 NOTE: COORDINATE SIZE OF JOIST HANGER ACCORDINGLY.
  
 ***CLARIFY ATTACHMENT OF WOOD POST TO BEAM. PROVIDE
 DETAIL. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO
 VERIFY COMPLIANCE WITH THE CALCULATED LOADS OF SEC.
 R301 OF 2004 FLORIDA RESIDENTIAL CODE. WHY IS THERE A
 LEDGER SHOWN INSTEAD OF A BEAM TO POST CONNECTION?.
 CLEARLY SPECIFY CONNECTIONS AT CORNER POSTS AND
 INTERMEDIATE POSTS.
  
 ****SPECIFY HOW MANY SCREWS ARE REQUIRED TO ATTACH 2X6
 WOOD DECK. TO VERIFY COMPLIANCE WITH UPLIFT LOADS OF
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 *****CLARIFY WHY DIMENSIONS SHOW 6" WHEN SHOWING THE
 WOOD POST IF THE POSTS ARE SPECIFIED AS 4X4 POSTS? SEE
 COMMENTS ON PLANS.
  
  
 E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 GUARDRAIL TO SHOW COMPLIANCE WITH TABLE R301.5, AND
 SECTION R312 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 5- SHEET 4.1:
 A) INFORMATION SHOWN ON EXISTING ROOF PLAN DOESN'T
 MATCH INFORMATION SHOWN ON CONNECTOR SCHEDULE. CLARIFY
 SCOPE OF WORK. COORDINATE WITH ITEM 2A ABOVE.
  
 B) REVISE NOTES AT BOTTOM OF CONNECTOR SCHEDULE. SEE
 COMMENTS ON PLANS. SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR MINIMUM NAIL SIZE/TYPE AND SPACING
 INCLUDING ON ROOF ZONE #3.
  
 C) COMPONENTS AND CLADDING PRESSURES ZONES TABLES FOR
 ROOF AND WALLS IS MISSING THE NAILING SPACING AT
 INTERMEDIATE SUPPORTS. IT ONLY CALLS FOR NAILING AT
 EDGES. SEE COMMENTS ON PLANS.
  
 D) CLARIFY WHY THE NAILING SPACING SHOWN ON WALLS
 COMPONENTS AND CLADDING TABLE IS CLOSER TOGETHER FOR
 WALL ZONE 4 THAN FOR WALL ZONE 5.
  
 6- SHEET 5.1:
 A) TYPICAL TWO STORY WALL SECTION:
 *CLEARLY SPECIFY WHAT'S NEW AND WHAT'S EXISTING.
 COORDINATE WITH ITEM 2A ABOVE.
  
 **SPECIFY ALL CONNECTORS FROM ROOF TO FOOTING TO SHOW
 CONTINUOUS LOAD PATH AS REQUIRED BY SEC. R601.2 OF 2004
 FLORIDA RESIDENTIAL CODE.
 NOTE: CLARIFY WHY ONLY SECOND FLOOR JOISTS ARE RESTING
 ON ONLY ONE TOP PLATE IF THIS IS A BEARING WALL?.
  
 ***SOFFIT AREA SPECIFIES 3"X16" VENTS AT 72"O.C..
 PROVIDE CALCULATIONS TO SHOW THAT THESE VENTS ARE
 ADEQUATE TO COMPLY WITH SEC. R806 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 SEE COMMENTS ON PLANS.
  
 B) DOOR AND WINDOWS JAMB DETAILS DON'T MATCH WITH
 TYPICAL WINDOW OPENING SECTION AND TYPICAL WALL FRAMING
 SECTION. REVISE AS REQUIRED TO MATCH. SEE COMMENTS ON
 PLANS AND RETURN REVIEWED SET AFTER PLANS ARE REVISED.
  
 7- BRING REVISED PLANS FOR HISTORIC REVIEW STAMP (5TH
 FLOOR) PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 8- OWES $1.70 FOR NEW BALCONY RADON FEES AS REQUIRED BY
 CHAPTER 10D-91 FLORIDA ADMINISTRATIVE CODE., SUBPART B.
  
 9- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) METAL ROOF AS SHOWN ON PLANS.
  
 B) ALL NEW EXTERIOR DOORS. CLEARLY IDENTIFY ENTRY DOORS
 AND BALCONY DOORS.
  
 C) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 D) STORM SHUTTERS IF WINDOWS AND DOORS WITH GLAZING
 DON'T HAVE IMPACT GLAZING.
 ***NOTE: PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED COPY. AND, CLEARLY MARK ON SHUTTERS DRAWINGS
 SPECIFIC MOUNTING CONDITIONS (EG: WALL MOUNTED, BUILD
 OUT, ETC) AND SPECIFIC ANCHOR TYPE AND SPACING TO BE
 USED TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER