Plan Review Notes
Plan Review Notes For Permit 08110374
Permit Number 08110374
Review Stop B
Sequence Number 1
Notes
Date Text
2008-11-19 10:36:282004 FBC W/2007 REVISIONS
 INSTALL ACCORDIONS AND STORM PANELS
  
 DENIED BY BUILDING
  
 1) THE NOA # HAS BEEN CORRECTED ON THE ACCORDION
 SCHEDULE. SEE RED-LINED CHANGES.
  
 2) WALL MOUNTS A AND B ARE FOR POURED CONCRETE ONLY AND
 THE SUBSTRATE WAS SPECIFIED IN THE SCHEDULE AS CONCRETE
 BLOCK. PLEASE CORRECT. THE FASTENER SPACING TABLES IN
 THE NOA SPECIFY IF THE MOUNT TYPES LISTED ARE FOR
 POURED CONCRETE ONLY OR ARE FOR BOTH POURED CONCRETE
 AND CONCRETE BLOCK.
  
 3) THE MOUNT TYPES SPECIFIED IN THE SCHEDULE AS WALL
 MOUNT B FOR THE BOTTOM IS INCORRECT. SEE THE
 INSTALLATION DRAWINGS IN THE PRODUCT APPROVAL. THERE
 ARE HEADER AND SILL INSTALLATIONS SHOWN. A AND B ARE
 BOTH HEADER OR FOR THE TOP. THE SILL AND FLOOR
 INSTALLATIONS ARE FOR THE BOTTOMS. PLEASE CORRECT
 SCHEDULE AND SPECIFY THE CORRECT FASTENER SPACINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]