Plan Review Notes For Permit 08110373 |
Permit Number |
08110373 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-11-19 09:44:18 | 2004 FBC W/2007 REVISIONS | | INSTALL ACCORDIONS AND STORM PANELS | | | | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | BE REQUIRED. | | | | 2) THE INSTALLATION SCHEDULE FOR THE BERTHA STORM | | PANELS DOES NOT SPECIFY THE SECTION # FROM THE PRODUCT | | APPROVAL FOR SHUTTER MOUNTING THAT WILL BE USED. THIS | | INFORMATION IS REQUIRED TO DETERMINE THE ANCHOR | | SPACINGS FROM THE TABLES IN THE PRODUCT APPROVAL. | | | | 3) THE STATE FL# IS INCORRECT ON THE STORM PANEL | | SCHEDULE AND HAS BEEN CORRECTED. SEE RED-LINED CHANGES. | | | | 4) THE NOA # HAS BEEN CORRECTED ON THE ACCORDION | | SCHEDULE. SEE RED-LINED CHANGES. | | | | 5) THE WALL MOUNT A IS FOR POURED CONCRETE ONLY AND THE | | SUBSTRATE WAS SPECIFIED IN THE SCHEDULE AS CONCRETE | | BLOCK. SEE RED-LINED CHANGES. THE FASTENER SPACING | | TABLES IN THE NOA SPECIFY IF THE MOUNT TYPES LISTED ARE | | FOR POURED CONCRETE ONLY OR ARE FOR BOTH POURED | | CONCRETE AND CONCRETE BLOCK. | | | | 6) THE ANCHOR SPACING SPECIFIED IN THE SCHEDULE FOR THE | | WALL MOUNT C WAS WRONG AND HAS BEEN CORRECTED. SEE | | RED-LINED CHANGES. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|