Plan Review Notes
Plan Review Notes For Permit 08110373
Permit Number 08110373
Review Stop B
Sequence Number 1
Notes
Date Text
2008-11-19 09:44:182004 FBC W/2007 REVISIONS
 INSTALL ACCORDIONS AND STORM PANELS
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) THE INSTALLATION SCHEDULE FOR THE BERTHA STORM
 PANELS DOES NOT SPECIFY THE SECTION # FROM THE PRODUCT
 APPROVAL FOR SHUTTER MOUNTING THAT WILL BE USED. THIS
 INFORMATION IS REQUIRED TO DETERMINE THE ANCHOR
 SPACINGS FROM THE TABLES IN THE PRODUCT APPROVAL.
  
 3) THE STATE FL# IS INCORRECT ON THE STORM PANEL
 SCHEDULE AND HAS BEEN CORRECTED. SEE RED-LINED CHANGES.
  
 4) THE NOA # HAS BEEN CORRECTED ON THE ACCORDION
 SCHEDULE. SEE RED-LINED CHANGES.
  
 5) THE WALL MOUNT A IS FOR POURED CONCRETE ONLY AND THE
 SUBSTRATE WAS SPECIFIED IN THE SCHEDULE AS CONCRETE
 BLOCK. SEE RED-LINED CHANGES. THE FASTENER SPACING
 TABLES IN THE NOA SPECIFY IF THE MOUNT TYPES LISTED ARE
 FOR POURED CONCRETE ONLY OR ARE FOR BOTH POURED
 CONCRETE AND CONCRETE BLOCK.
  
 6) THE ANCHOR SPACING SPECIFIED IN THE SCHEDULE FOR THE
 WALL MOUNT C WAS WRONG AND HAS BEEN CORRECTED. SEE
 RED-LINED CHANGES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]