Plan Review Notes
Plan Review Notes For Permit 08110321
Permit Number 08110321
Review Stop P
Sequence Number 1
Notes
Date Text
2008-12-01 16:34:32DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. APPLICATION DOES NOT INCLUDE PLUMBING IN THE
 DESCRIPTION OF THE PROJECT. APPLICATION REQUIRES THAT
 APPLICANT DESCRIBES THE PROJECT IN DETAIL AND TO
 INDICATE IF THERE IS A CHANGE OF OCCUPANCY OR NOT.
 SECTION 106.1.2.
  
 2. THE SINK ADDED TO THE LOUNGE SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL & ELEVATION SHOWING COMPLIANCE
 WITH SECTION 11-4.24 WITH ALL SUBSECTIONS.
  
 3. SEE COMMENT 5 OF THE BUILDING PLAN REVIEW ABOUT THE
 VALUE OF THE PERMIT APPLICATION. SECTION 108.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  