Plan Review Notes
Plan Review Notes For Permit 08110263
Permit Number 08110263
Review Stop P
Sequence Number 2
Notes
Date Text
2009-02-20 10:29:41DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 PLAN REVIEW ONLY:
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT A.5 SHOW COMPLIANCE WITH SECTION 11-4.24.3 KNEE
 CLEARANCE (27" REQD), AND 11-4.24.6 EXPOSED PIPES &
 SURFACES.
 ****RESPONSE NOTED, BUT SECTION 1-4.24.6 NOT ADDRESSED.
  
 3. SHT P.1 THE SANITARY AND TRAP ARE NOT SHOWN AT THE
 SINK IN ROOM 121. PLEASE CLARIFY SECTIONS 106.1.1,
 701.1 & 1002.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PIPING
 AND TRAP STILL NOT SHOWN AT THE SINK. THE PIPING AND
 TRAP ARE SHOWN OUTSIDE THE CABINET.
  
 4. OK
 5. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  