Plan Review Notes For Permit 08110263
Permit Number 08110263
Review Stop P
Sequence Number 1
Notes
Date Text
2008-12-18 10:19:51DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 PLAN REVIEW ONLY:
  
 1. SHT A.3 SHOW COMPLIANCE WITH SECTION 11-4.16.5 FLUSH
 CONTROLS.
  
 2. SHT A.5 SHOW COMPLIANCE WITH SECTION 11-4.24.3 KNEE
 CLEARANCE (27" REQD), AND 11-4.24.6 EXPOSED PIPES &
 SURFACES.
  
 3. SHT P.1 THE SANITARY AND TRAP ARE NOT SHOWN AT THE
 SINK IN ROOM 121. PLEASE CLARIFY SECTIONS 106.1.1,
 701.1 & 1002.1.
  
 4. SHTS T.1 & LS.1 PLEASE INDICATE 2007 REVISIONS WITH
 THE FBC-2004 IN THE CODE SUMMARY.
  
 5. SHT P.3 PLEASE INDICATE THE REQUIRED INSULATION FOR
 THE HOT WATER PIPING WITH A NOTE ON THE WATER RISER
 DIAGRAM AS INDICATED IN THE INPUT DATA REPORT SHT 9 FOR
 THE PIPING. CHAPTER 13.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  