Plan Review Notes For Permit 08110263
Permit Number 08110263
Review Stop M
Sequence Number 1
Notes
Date Text
2008-12-06 12:52:03REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: P/F
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLANS HAVE BEEN REVIEWED FOR COMPLIANCE AND PASSED.
 HOWEVER, PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN
 REVIEW. NO PERMIT APPLICATION HAS BEEN SUBMITTED. PLANS
 WILL REMIAN IN FAILED STATUS PENDING SUBMISSION OF
 PERMIT APPLICATION.
  
 NOTE: ENERGY CALCULATIONS WERE NOT REVIEWED FOR CODE
 COMPLIANCE. IT IS NOT CLEAR AT THIS TIME WHETHER THIS
 WORK QUALIFIES AS A "RENOVATION" AS DEFINED IN FBCB
 13-202. IF THIS PROJECT IS NOT A RENOVATION UNDER THIS
 DEFINITION, SEE FBCB 13-101.6 BELOW FOR MINIMUM
 REQUIREMENTS. ENOUGH INFORMATION HAS BEEN PROVIDED ON
 PLANS TO DEMONSTRATE COMPLIANCE WITH THE REQUIREMENTS
 OF FBCB 13-101.6. THEREFORE, NO ENERGY OR COOLING LOAD
 CALCULATIONS ARE REQUIRED.
  
 13-101.6 BUILDING SYSTEMS.
 THERMAL EFFICIENCY STANDARDS ARE SET FOR THE FOLLOWING
 BUILDING SYSTEMS WHERE NEW PRODUCTS ARE INSTALLED OR
 REPLACED IN EXISTING BUILDINGS, AND FOR WHICH A PERMIT
 MUST BE OBTAINED. SUCH SYSTEMS SHALL MEET THE MINIMUM
 EFFICIENCIES ALLOWED FOR THAT SYSTEM ON FORM 400C FOR
 COMMERCIAL BUILDINGS AND ON FORM 600C FOR RESIDENTIAL
 BUILDINGS.
 1. HEATING, VENTILATING OR AIR CONDITIONING SYSTEMS;
 2. SERVICE WATER OR POOL HEATING SYSTEMS;
 3. ELECTRICAL SYSTEMS AND MOTORS;
 4. LIGHTING SYSTEMS.
 EXCEPTIONS:
 1. WHERE PART OF A FUNCTIONAL UNIT IS REPAIRED OR
 REPLACED. FOR EXAMPLE, REPLACEMENT OF AN ENTIRE HVAC
 SYSTEM IS NOT REQUIRED BECAUSE A NEW COMPRESSOR OR
 OTHER PART DOES NOT MEET CODE WHEN INSTALLED WITH AN
 OLDER SYSTEM.
 2. WHERE EXISTING COMPONENTS ARE UTILIZED WITH A
 REPLACEMENT SYSTEM, SUCH AS AIR DISTRIBUTION SYSTEM
 DUCTS OR ELECTRICAL WIRING FOR LIGHTS, SUCH COMPONENTS
 OR CONTROLS NEED NOT MEET CODE IF MEETING CODE WOULD
 REQUIRE THAT COMPONENT?S REPLACEMENT.
 3. REPLACEMENT EQUIPMENT THAT WOULD REQUIRE EXTENSIVE
 REVISIONS TO OTHER SYSTEMS, EQUIPMENT OR ELEMENTS OF A
 BUILDING WHERE SUCH REPLACEMENT IS A LIKE-FOR-LIKE
 REPLACEMENT, SUCH AS THROUGH-THE-WALL CONDENSING UNITS
 AND PTACS, CHILLERS, AND COOLING TOWERS IN CONFINED
 SPACES.
 4. HVAC EQUIPMENT SIZING CALCULATIONS ARE NOT REQUIRED
 FOR SYSTEMS INSTALLED IN EXISTING BUILDINGS NOT MEETING
 THE DEFINITION OF RENOVATION IN SECTION 202.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]