Plan Review Notes For Permit 08110263 |
Permit Number |
08110263 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-12-11 14:04:35 | PLANS APPEAR TO BE CODE COMPLIANT HOWEVER PLEASE SEE | | THE FOLLOWING: | | | | 1) TITLE SHEET INDICATES THAT PROJECT IS PROTECTED BY | | AN AUTOMATIC FIRE SPRINKLER SYSTEM. WHEN PLANS ARE | | SUBMITTED FOR PERMIT REVIEW, PLEASE SHOW THE FIRE | | SPRINKLER LAYOUT. THIS CAN BE ILLUSTRATED ON THE | | REFLECTED CEILING PLAN. IN ADDITION, SEPARATE SHOP | | DRAWINGS AND PERMIT WILL BE REQUIRED FOR FIRE SPRINKLER | | REMODEL. | | | | 2) THE DOOR TO DATA ROOM 113 SEEMS TO EXTEND GREATER | | THAN 1/2 THE WIDTH OF THE CORRIDOR. SEE NFPA 101, | | SEC.7.2.1.4.4. | | | | | | PLANS WILL REMAIN IN FAILED STATUS UNTIL SUBMITTED AND | | APPROVED FOR PERMIT REVIEW. | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|