Plan Review Notes
Plan Review Notes For Permit 08110263
Permit Number 08110263
Review Stop E
Sequence Number 1
Notes
Date Text
2008-12-03 08:40:59 
 ** DENIED REVIEW**
  
  
  
 1) NOTE: PLANS SUBMITTED FOR PLAN REVIEW ONLY. EVEN
 ONCE ALL ITEMS FOR CODE COMPLIANCE ARE MET AND PERMIT
 APPLICATION HAS NOT BEEN MADE REVIEW WILL REMAIN IN
 FAILED STATUS. ITEMS SUCH AS LICENSING, CODES ETC ARE
 REVIEWED AT TIME OF APPLICATION.
  
 2) NOTE: PLEASE BE SURE THE RELEVANT CODES ARE
 ADJUSTED. CODES ON THE COVER SHEET COMPARED TO
 ELECTRICAL PLANS FOR EXAMPLES ARE NOT THE SAME.
 PLEASE SEE COVER SHEET WHICH SHOULD REFLECT 2004 FBC W/
 2007 REVISIONS.
 PLEASE SEE COVER SHEET WHICH SHOULD REFLECT THE 2005
 NFPA-70 (NATIONAL ELECTRICAL CODE) PLANS SHOW 2002.
 LIFE SAFETY SHEET DOES CONTAIN THE CORRECT 2005 NEC
 HOWEVER ELECTRICAL PLANS STATE *LATEST*.
 PLEASE ADJUST ALL SHEETS AS APPLICABLE.
  
 3) NOTE: PLEASE SEE FBC 13-101.1.3 AND SECTION 202 FOR
 DEFINITIONS. PLEASE EXPLAIN HOW FLA-COM FORM *B* BE
 USED. PLEASE KNOW BASED ON DEFINITIONS, PLANS
 SUBMITTED, NO PERMIT APPLICATION FOR VALUE THE METHOD
 *B* MAY NOT BE USED.
 PLEASE SEE 13-400.C FOR EXAMPLE WHICH MENTIONS WHEN NOT
 MEETING THE DEFINITION OF A RENOVATED BUILDING, BASIC
 PRESCRIPTIVE REQUIREMENTS MUST BE MET.
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 TABLES 13-415.2.B, OR 13-415.2.C. PLEASE CALL TO GO
 OVER AS SOME INFORMATION ON E3 IS SHOWN.
  
 4) NOTE: PLEASE SEE FBC 11-4.27.4 AS THE TIMER TYPE
 DEVICES AS SHOWN ARE NOT PERMITTED TO BE THE TYPE WHICH
 WOULD REQUIRE TWISTING ACTION ETC. PLEASE SEE SECTION
 GIVEN AS ALL CONTROLS FOR LIGHTING ETC NEED TO MEET ADA
 REQUIREMENTS.
 PLEASE ADJUST NOTES AND SPECIFICS FOR DEVICES.
  
 5) NOTE: PLEASE PROVIDE WALL/FLOOR PENETRATION DETAILS
 FOR LISTED WALL ASSEMBLIES. 300.21. PLEASE SEE
 COMMENTARY IN NEC HANDBOOK WHICH WILL REFERENCE
 ACCEPTABLE STANDARDS.
 IF THE SAME DETAILS ON A4 ARE TO BE USED PLEASE MAKE
 NOTE ON ELECTRICAL PLANS REFERENCING TO THIS SHEET.
  
 6) NOTE: PLEASE CLARIFY THE SECTION ON E3 SHOWN AS
 *DEMAND LOAD* WHICH SHOWS EXISTING FEEDERS AS 4-
 500MCM. WHAT FEEDERS ARE THESE AS THE NEW FEEDERS ON
 RISER FROM GUTTER ARE NOT THE SAME.
  
 7) NOTE: PLEASE NOTE A *FLOATING NEUTRAL KIT* REQUIRED
 AT THE TENANT METER. 250.6,250.24 ETC.
  
 8) NOTE: PLEASE SHOW ANY NEW OR EXISTING FIRE ALARM
 DEVICES. PLEASE BE SURE TO SEE FBC 11-4.28.1,.2 AND .3
 FOR MINIMUM LEVELS FOR ADA COMPLIANCE.
 (IF APPLICABLE IN THIS BUILDING).
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  