2008-12-03 08:40:59 | |
| ** DENIED REVIEW** |
| |
| |
| |
| 1) NOTE: PLANS SUBMITTED FOR PLAN REVIEW ONLY. EVEN |
| ONCE ALL ITEMS FOR CODE COMPLIANCE ARE MET AND PERMIT |
| APPLICATION HAS NOT BEEN MADE REVIEW WILL REMAIN IN |
| FAILED STATUS. ITEMS SUCH AS LICENSING, CODES ETC ARE |
| REVIEWED AT TIME OF APPLICATION. |
| |
| 2) NOTE: PLEASE BE SURE THE RELEVANT CODES ARE |
| ADJUSTED. CODES ON THE COVER SHEET COMPARED TO |
| ELECTRICAL PLANS FOR EXAMPLES ARE NOT THE SAME. |
| PLEASE SEE COVER SHEET WHICH SHOULD REFLECT 2004 FBC W/ |
| 2007 REVISIONS. |
| PLEASE SEE COVER SHEET WHICH SHOULD REFLECT THE 2005 |
| NFPA-70 (NATIONAL ELECTRICAL CODE) PLANS SHOW 2002. |
| LIFE SAFETY SHEET DOES CONTAIN THE CORRECT 2005 NEC |
| HOWEVER ELECTRICAL PLANS STATE *LATEST*. |
| PLEASE ADJUST ALL SHEETS AS APPLICABLE. |
| |
| 3) NOTE: PLEASE SEE FBC 13-101.1.3 AND SECTION 202 FOR |
| DEFINITIONS. PLEASE EXPLAIN HOW FLA-COM FORM *B* BE |
| USED. PLEASE KNOW BASED ON DEFINITIONS, PLANS |
| SUBMITTED, NO PERMIT APPLICATION FOR VALUE THE METHOD |
| *B* MAY NOT BE USED. |
| PLEASE SEE 13-400.C FOR EXAMPLE WHICH MENTIONS WHEN NOT |
| MEETING THE DEFINITION OF A RENOVATED BUILDING, BASIC |
| PRESCRIPTIVE REQUIREMENTS MUST BE MET. |
| PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER |
| TABLES 13-415.2.B, OR 13-415.2.C. PLEASE CALL TO GO |
| OVER AS SOME INFORMATION ON E3 IS SHOWN. |
| |
| 4) NOTE: PLEASE SEE FBC 11-4.27.4 AS THE TIMER TYPE |
| DEVICES AS SHOWN ARE NOT PERMITTED TO BE THE TYPE WHICH |
| WOULD REQUIRE TWISTING ACTION ETC. PLEASE SEE SECTION |
| GIVEN AS ALL CONTROLS FOR LIGHTING ETC NEED TO MEET ADA |
| REQUIREMENTS. |
| PLEASE ADJUST NOTES AND SPECIFICS FOR DEVICES. |
| |
| 5) NOTE: PLEASE PROVIDE WALL/FLOOR PENETRATION DETAILS |
| FOR LISTED WALL ASSEMBLIES. 300.21. PLEASE SEE |
| COMMENTARY IN NEC HANDBOOK WHICH WILL REFERENCE |
| ACCEPTABLE STANDARDS. |
| IF THE SAME DETAILS ON A4 ARE TO BE USED PLEASE MAKE |
| NOTE ON ELECTRICAL PLANS REFERENCING TO THIS SHEET. |
| |
| 6) NOTE: PLEASE CLARIFY THE SECTION ON E3 SHOWN AS |
| *DEMAND LOAD* WHICH SHOWS EXISTING FEEDERS AS 4- |
| 500MCM. WHAT FEEDERS ARE THESE AS THE NEW FEEDERS ON |
| RISER FROM GUTTER ARE NOT THE SAME. |
| |
| 7) NOTE: PLEASE NOTE A *FLOATING NEUTRAL KIT* REQUIRED |
| AT THE TENANT METER. 250.6,250.24 ETC. |
| |
| 8) NOTE: PLEASE SHOW ANY NEW OR EXISTING FIRE ALARM |
| DEVICES. PLEASE BE SURE TO SEE FBC 11-4.28.1,.2 AND .3 |
| FOR MINIMUM LEVELS FOR ADA COMPLIANCE. |
| (IF APPLICABLE IN THIS BUILDING). |
| |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |