2008-12-10 07:49:40 | BUILDING PLAN REVIEW |
| PERMIT: 08110263 |
| ADD: 4631 N CONGRESS AV |
| CONT: "PLAN REVIEW/ |
| TEL: (561)635-6935/ NAT HEALY |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 1C) : PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS NOT INCLUDING ALL |
| AMENDMENTS. |
| |
| 2) ENERGY CALCULATIONS PLEASE REVIEW 13-400.0.C.4 |
| RENOVATED BUILDINGS. |
| RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION |
| 202), MEET THE EFFICIENCIES LISTED ON FORM 400C FOR |
| COMPONENTS BEING CHANGED OR SHALL COMPLY WITH THE |
| ENVELOPE OR SYSTEMS CRITERIA IN METHOD B OF FLA/COM FOR |
| THE COMPONENTS BEING CHANGED. EXISTING BUILDINGS NOT |
| MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW |
| HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING |
| SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE |
| MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE |
| SYSTEM(S) BEING CHANGED. |
| |
| RENOVATION. ANY STRUCTURAL REPAIR, RECONSTRUCTION OR |
| RESTORATION TO A STRUCTURE, THE COSTS OF WHICH EQUALS |
| OR EXCEEDS, OVER A ONE-YEAR PERIOD, A CUMULATIVE TOTAL |
| OF 30 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE |
| WHEN THAT VALUE IS ASSESSED, EITHER: |
| 1. BEFORE THE IMPROVEMENT OR REPAIR IS STARTED; OR |
| 2. BEFORE THE DAMAGE OCCURRED, IF THE STRUCTURE HAS |
| BEEN DAMAGED. |
| FOR THE PURPOSES OF THIS CODE, RENOVATION OCCURS WHEN |
| THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR |
| OTHER STRUCTURAL PART OR MECHANICAL SYSTEM OF THE |
| BUILDING COMMENCES, WHETHER OR NOT THAT ALTERATION |
| AFFECTS THE EXTERNAL DIMENSIONS OF THE STRUCTURE. |
| |
| WITH THIS ONLY BEING A PLAN REVIEW AND NOT A PERMIT |
| APPLICATION IT APPEARS THE WORK TO BE COVERED UNDER |
| THIS PERMIT WILL NOT MEET THE 30% OF THE VALUE OF THE |
| BUILDING, REQUIRING FORM 400 C, ONCE THE VALUE IS KNOWN |
| WE WILL HAVE THE CRITERIA TO ASSESS WHICH METHOD B OR C |
| SHOULD HAVE BEEN USED. |
| |
| 3) SHEET A-1 DOES NOT INDICATE WHAT AREAS ARE ALREADY |
| THERE AND WHAT IS TO BE CONSIDERED NEW WORK. ADDITIONAL |
| INFORMATION REQUIRED 106.1.2. |
| |
| 4) SHEET A-3 DETAIL 4 & 5 BOTH INDICATE SOFFIT DETAILS |
| BUT DO NOT PROVIDE WHAT TYPE OF ATTACHMENT METHOD WILL |
| BE USED TO INSTALL SOFFITS TO DECK ABOVE? 2508.1, TABLE |
| 2508.1 & GA-216. |
| |
| 5) SHEET A-4 INDICATES WALL ASSEMBLIES FOR RATED WALLS |
| BUT DOES NOT PROVIDE FLOOR PENETRATIONS FOR HORIZONTAL |
| ASSEMBLIES. 712.4.1.2. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |