2008-12-10 07:49:40BUILDING PLAN REVIEW
 PERMIT: 08110263
 ADD: 4631 N CONGRESS AV
 CONT: "PLAN REVIEW/
 TEL: (561)635-6935/ NAT HEALY
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) : PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS NOT INCLUDING ALL
 AMENDMENTS.
  
 2) ENERGY CALCULATIONS PLEASE REVIEW 13-400.0.C.4
 RENOVATED BUILDINGS.
 RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION
 202), MEET THE EFFICIENCIES LISTED ON FORM 400C FOR
 COMPONENTS BEING CHANGED OR SHALL COMPLY WITH THE
 ENVELOPE OR SYSTEMS CRITERIA IN METHOD B OF FLA/COM FOR
 THE COMPONENTS BEING CHANGED. EXISTING BUILDINGS NOT
 MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW
 HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING
 SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE
 MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE
 SYSTEM(S) BEING CHANGED.
  
 RENOVATION. ANY STRUCTURAL REPAIR, RECONSTRUCTION OR
 RESTORATION TO A STRUCTURE, THE COSTS OF WHICH EQUALS
 OR EXCEEDS, OVER A ONE-YEAR PERIOD, A CUMULATIVE TOTAL
 OF 30 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE
 WHEN THAT VALUE IS ASSESSED, EITHER:
 1. BEFORE THE IMPROVEMENT OR REPAIR IS STARTED; OR
 2. BEFORE THE DAMAGE OCCURRED, IF THE STRUCTURE HAS
 BEEN DAMAGED.
 FOR THE PURPOSES OF THIS CODE, RENOVATION OCCURS WHEN
 THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR
 OTHER STRUCTURAL PART OR MECHANICAL SYSTEM OF THE
 BUILDING COMMENCES, WHETHER OR NOT THAT ALTERATION
 AFFECTS THE EXTERNAL DIMENSIONS OF THE STRUCTURE.
  
 WITH THIS ONLY BEING A PLAN REVIEW AND NOT A PERMIT
 APPLICATION IT APPEARS THE WORK TO BE COVERED UNDER
 THIS PERMIT WILL NOT MEET THE 30% OF THE VALUE OF THE
 BUILDING, REQUIRING FORM 400 C, ONCE THE VALUE IS KNOWN
 WE WILL HAVE THE CRITERIA TO ASSESS WHICH METHOD B OR C
 SHOULD HAVE BEEN USED.
  
 3) SHEET A-1 DOES NOT INDICATE WHAT AREAS ARE ALREADY
 THERE AND WHAT IS TO BE CONSIDERED NEW WORK. ADDITIONAL
 INFORMATION REQUIRED 106.1.2.
  
 4) SHEET A-3 DETAIL 4 & 5 BOTH INDICATE SOFFIT DETAILS
 BUT DO NOT PROVIDE WHAT TYPE OF ATTACHMENT METHOD WILL
 BE USED TO INSTALL SOFFITS TO DECK ABOVE? 2508.1, TABLE
 2508.1 & GA-216.
  
 5) SHEET A-4 INDICATES WALL ASSEMBLIES FOR RATED WALLS
 BUT DOES NOT PROVIDE FLOOR PENETRATIONS FOR HORIZONTAL
 ASSEMBLIES. 712.4.1.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.