2009-02-02 15:22:54 | ** DENIED 2ND REVIEW ** |
| |
| 1) NOTE: *** SAME EXACT NOTES FROM PREVIOUS REVIEW. NO |
| CHANGES WERE MADE OR CORRECTIONS MADE TO PLANS. THIS IS |
| A CHANGE IN OCCUPANCY TO LOCATION. PLEASE SEE FBC |
| CHAPTER 3, 13 FOR CHANGES IN OCCUPANCY. PLEASE SEE FBC |
| EXISTING BUILDING CODE CHAPTER 8 FOR CHANGES IN |
| OCCUPANCY. |
| PLEASE SEE NFPA-72, 70, 101 ALSO FOR MINIMUM |
| REQUIREMENTS. |
| PLEASE SUBMIT COMPLETE ELECTRICAL PLANS FOR ALL NEW AS |
| THIS IS NOW A COMMERCIAL OCCUPANCY AND ALL PLANS NEED |
| TO SHOW MINIMUM COMPLIANCE WITH THIS TYPE OF OCCUPANCY. |
| LOAD CALCULATIONS, NEC 220 |
| CIRCUITING, NEC 240.4,310.16,408.4 ETC |
| ENERGY EFFICIENCY, CHAPTER 13, LIGHTING CONTROLS |
| 13-415.1.ABC.1 |
| PANELS, 408.4, |
| PERFORMANCE CALCULATIONS, 13-415.2 |
| NOTES ARE BROAD AS NO INFORMATION WAS SHOWN. |
| ** MAY NOT QUOTE CODES FOR MINIMUM DESIGN IN LIEU OF |
| SPECIFIC CODE COMPLIANCE DETAILS. |
| |
| |
| ** IT IS NOTED ONCE AGAIN THAT AS THERE ARE SEVERAL |
| UNKNOWN FACTORS AND MISSING INFORMATION, THERE MAY VERY |
| WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN |
| NOT BE MADE AT THIS TIME. |
| |
| 2) NOTE: PLANS WHICH WERE BROUGHT BACK IN AND SUBMITTED |
| ARE NOT SIGNED, DATED OR SEALED BY THE DESIGN |
| PROFESSIONAL OF RECORD. |
| SEE FS 481.221 |
| |
| 3) NOTE: VALUE FOR SCOPE OF WORK INCREASED HOWEVER WORK |
| AS NOTED IS STILL LOW AND UNKNOWN WORK IS NOT INCLUDED. |
| FBC 108.3 |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |