Plan Review Notes
Plan Review Notes For Permit 08110248
Permit Number 08110248
Review Stop E
Sequence Number 2
Notes
Date Text
2009-02-02 15:22:54** DENIED 2ND REVIEW **
  
 1) NOTE: *** SAME EXACT NOTES FROM PREVIOUS REVIEW. NO
 CHANGES WERE MADE OR CORRECTIONS MADE TO PLANS. THIS IS
 A CHANGE IN OCCUPANCY TO LOCATION. PLEASE SEE FBC
 CHAPTER 3, 13 FOR CHANGES IN OCCUPANCY. PLEASE SEE FBC
 EXISTING BUILDING CODE CHAPTER 8 FOR CHANGES IN
 OCCUPANCY.
 PLEASE SEE NFPA-72, 70, 101 ALSO FOR MINIMUM
 REQUIREMENTS.
 PLEASE SUBMIT COMPLETE ELECTRICAL PLANS FOR ALL NEW AS
 THIS IS NOW A COMMERCIAL OCCUPANCY AND ALL PLANS NEED
 TO SHOW MINIMUM COMPLIANCE WITH THIS TYPE OF OCCUPANCY.
 LOAD CALCULATIONS, NEC 220
 CIRCUITING, NEC 240.4,310.16,408.4 ETC
 ENERGY EFFICIENCY, CHAPTER 13, LIGHTING CONTROLS
 13-415.1.ABC.1
 PANELS, 408.4,
 PERFORMANCE CALCULATIONS, 13-415.2
 NOTES ARE BROAD AS NO INFORMATION WAS SHOWN.
 ** MAY NOT QUOTE CODES FOR MINIMUM DESIGN IN LIEU OF
 SPECIFIC CODE COMPLIANCE DETAILS.
  
  
 ** IT IS NOTED ONCE AGAIN THAT AS THERE ARE SEVERAL
 UNKNOWN FACTORS AND MISSING INFORMATION, THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN
 NOT BE MADE AT THIS TIME.
  
 2) NOTE: PLANS WHICH WERE BROUGHT BACK IN AND SUBMITTED
 ARE NOT SIGNED, DATED OR SEALED BY THE DESIGN
 PROFESSIONAL OF RECORD.
 SEE FS 481.221
  
 3) NOTE: VALUE FOR SCOPE OF WORK INCREASED HOWEVER WORK
 AS NOTED IS STILL LOW AND UNKNOWN WORK IS NOT INCLUDED.
 FBC 108.3
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  