2008-11-19 09:36:00** FAILED REVIEW **
  
 **
  
  
 1) NOTE: PLANS SHOW REMOVAL OF KITCHENS FROM BOTH UNITS
 WHICH ARE DWELLING UNITS. WHAT WILL THE NEW OCCUPANCY
 BE? FBC 303.1
 THE WALLS AND OTHER LOCATIONS ARE BEING FINISHED TO AND
 END USE HOWEVER PLEASE SEE SECTION ABOVE AS THE
 OCCUPANCY WHICH WILL BE CHANGING FROM DWELLING TO
 OTHER.
 PLEASE SEE FBC CHAPTER 13 FOR ANY NEW BEING INSTALLED.
 PLEASE SEE FBC EXISTING BUILDING CODE CHAPTER 8 FOR USE
 AND CLASSIFICATION TO POSSIBLE HIGHER HAZARD.
  
 2) NOTE: PLANS WILL BE REQUIRED TO SHOW THE FOLLOWING
 CODES:
 2002 NFPA_72
 2003 NFPA-101
 2005 NFPA-70
  
 3) NOTE: PLEASE SEE CHAPTER 9 OF THE FBC FOR FIRE ALARM
 DEVICES ALONG WITH CHAPTER 11, SPECIFICALLY
 11-4.28.1,.2 AND .3.
  
 4) NOTE: THE APPLIED VALUATION SHALL INCLUDE ALL LABOR,
 MATERIALS, EQUIPMENT, DESIGN COST ETC EVEN IF ANY OF
 THESE ITEMS ARE OWNER SUPPLIED.
 THE APPLIED VALUE OF $2,300.00 IS LOW.
 FBC 108.3
  
 5) NOTE: IT IS IMPORTANT TO KNOW AS THERE ARE SEVERAL
 UNKNOWN FACTORS AT THIS TIME THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH COULD NOT BE
 MADE AT THIS TIME.
 PLEASE CALL TO GO OVER ANY ITEMS OR QUESTIONS WHICH MAY
 HELP ALLEVIATE ANY DELAY OF THE PROJECT.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  