2008-11-19 09:36:00 | ** FAILED REVIEW ** |
| |
| ** |
| |
| |
| 1) NOTE: PLANS SHOW REMOVAL OF KITCHENS FROM BOTH UNITS |
| WHICH ARE DWELLING UNITS. WHAT WILL THE NEW OCCUPANCY |
| BE? FBC 303.1 |
| THE WALLS AND OTHER LOCATIONS ARE BEING FINISHED TO AND |
| END USE HOWEVER PLEASE SEE SECTION ABOVE AS THE |
| OCCUPANCY WHICH WILL BE CHANGING FROM DWELLING TO |
| OTHER. |
| PLEASE SEE FBC CHAPTER 13 FOR ANY NEW BEING INSTALLED. |
| PLEASE SEE FBC EXISTING BUILDING CODE CHAPTER 8 FOR USE |
| AND CLASSIFICATION TO POSSIBLE HIGHER HAZARD. |
| |
| 2) NOTE: PLANS WILL BE REQUIRED TO SHOW THE FOLLOWING |
| CODES: |
| 2002 NFPA_72 |
| 2003 NFPA-101 |
| 2005 NFPA-70 |
| |
| 3) NOTE: PLEASE SEE CHAPTER 9 OF THE FBC FOR FIRE ALARM |
| DEVICES ALONG WITH CHAPTER 11, SPECIFICALLY |
| 11-4.28.1,.2 AND .3. |
| |
| 4) NOTE: THE APPLIED VALUATION SHALL INCLUDE ALL LABOR, |
| MATERIALS, EQUIPMENT, DESIGN COST ETC EVEN IF ANY OF |
| THESE ITEMS ARE OWNER SUPPLIED. |
| THE APPLIED VALUE OF $2,300.00 IS LOW. |
| FBC 108.3 |
| |
| 5) NOTE: IT IS IMPORTANT TO KNOW AS THERE ARE SEVERAL |
| UNKNOWN FACTORS AT THIS TIME THERE MAY VERY WELL BE NEW |
| COMMENTS ON THE FOLLOWING REVIEW WHICH COULD NOT BE |
| MADE AT THIS TIME. |
| PLEASE CALL TO GO OVER ANY ITEMS OR QUESTIONS WHICH MAY |
| HELP ALLEVIATE ANY DELAY OF THE PROJECT. |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |