Plan Review Notes
Plan Review Notes For Permit 08110248
Permit Number 08110248
Review Stop B
Sequence Number 1
Notes
Date Text
2008-11-25 07:59:06 
 BUILDING PLAN REVIEW
 PERMIT: 08110248
 ADD: 801 S. OLIVE AVE #110 &111
 CONT: T.M. MOTTLEY CONST.
 TEL: (561)502-1986
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 11-25-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) SUBMIT AN EXISTING AND A PROPOSED FLOOR AND
 ELEVATION PLAN OF BOTH UNITS INDICATING THE PROPOSED
 WORK. THE DRAWINGS NEED TO SHOW THE ENTIRE LAYOUT OF
 BOTH UNITS. SHOW IN DETAIL HOW THE STRUCTURAL INTEGRITY
 OF THE CONCRETE WALL WILL BE MAINTAINED ONCE THE PASS
 THROUGH IS CREATED. PROVIDE ELEVATION DRAWINGS.
 ADDITIONAL INFORMATION IS REQUIRED 106.1.2*
  
 3) A 'UNITY OF TITLE' SHALL BE RECORDED AT THE COUNTY
 COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY OF
 TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
  
 4) THE DRAWINGS INDICATE REMOVING THE KITCHEN IN BOTH
 DWELLING UNITS WHICH MEANS THERE WILL BE A CHANGE OF
 OCCUPANCY OF EACH SPACE.
  
 5) STATE CLEARLY ON THE PLANS IF THERE WILL BE A CHANGE
 OF OCCUPANCY TO THE SPACE, IF THERE WILL BE A CHANGE OF
 OCCUPANCY, INDICATE THE TYPE OF OCCUPANCY PER FBC
 CHAPTER 3 ON THE PLANS.
  
 6) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 7) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD) MARSHALL- SWIFT AND MEANS COST
 ANALYSIS SERVICES PER 108.3*
  
 8) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  