2008-11-18 13:44:19 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| 1. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| SECTION *106.3.4.3. (NOTE: THE PRINTED NAME AND DATE |
| ARE NOT INDICATED.) |
| |
| 3. PER FBC MECHANICAL, SECTION 303.9.4 PROTECTION FROM |
| DAMAGE. APPLIANCES (WATER HATERE IN GARAGE) SHALL NOT |
| BE INSTALLED IN A LOCATION WHERE SUBJECT TO MECHANICAL |
| DAMAGE UNLESS PROTECTED BY APPROVED BARRIERS. (CAN BE |
| PROVISO'D). |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |