2008-11-14 15:09:21RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- ACCORDION SHUTTERS PRODUCT APPROVAL FL5133:
 SHEETS SUBMITTED ARE 1 THRU 8 OF 16 OF DRAWING 05-208.
 THEY ARE FOR MID-RISE BERTHA ACCORDION SHUTTERS. THIS
 HOUSE IS A ONE STORY BUILDING, NOT A MID-RISE BUILDING.
 NEED TO PROVIDE PROPER DRAWINGS (9 THRU 16 OF 16) WHICH
 ARE THE DRAWINGS THAT APPLY TO THIS PROJECT.
  
 2- INSTALLATION SCHEDULE SUBMITTED FOR ACCORDION
 SHUTTERS: CLEARLY IDENTIFY SUBSTRATE WHERE SHUTTERS ARE
 GOING TO BE ATTACHED. EG: CONCRETE, CONCRETE BLOCK OR
 WOOD. COLUMN WAS LEFT BLANK. NEED THIS INFORMATION TO
 VERIFY COMPLIANCE WITH PRODUCT APPROVAL AND DESIGN
 PRESSURES AS REQUIRED BY SEC. R301 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 NOTE: TOP AND BOTTOM SUBSTRATE MUST BE POURED CONCRETE.
 FILLED CELLS DON'T COUNT AS CONCRETE. NEED TO USE
 MASONRY ANCHOR SCHEDULE OR PROVIDE PROOF/TESTING THAT
 FILLED CELLS HAVE THE SAME OR MORE STRENGTH THAN
 CONCRETE.
  
 3- STORM PANELS:
 A) FOR A 122" PANEL SPAN NEED TO USE CORRECT ANCHOR
 SCHEDULE. SEE ANCHOR SCHEDULE ON SHEET 11 OF 17 AND
 REVISE INSTALLATION SCHEDULE AS REQUIRED.
 B) CLEARLY MARK SPECIFIC CONNECTION AT TOP AND BOTTOM.
 EG: 3A (TOP) AND 2(BOTTOM).
 C) CLEARLY IDENTIFY SUBSTRATE TO RECEIVE SHUTTERS AT
 TOP AND BOTTOM. EG: CONCRETE OR MASONRY.
 NOTE: FILLED CELLS NEED TO USE MASONRY ANCHOR SPACING
 OR PROVIDE PROOF THAT FILLED CELLS ARE EQUIVALENT OR
 STRONGER THAN POURED CONCRETE.
 D) REVISE PANEL SPAN ON INSTALLATION SCHEDULE
 SUBMITTED. IF THE EDGE DISTANCE IS 3.5", THEN THE PANEL
 SPAN NEEDS TO BE COORDINATED WITH THE OPENING SIZE AND
 THE EDGE DISTANCE. EDGE DISTANCE DOESN'T INCLUDE STUCCO
 THICKNESS. ALSO, THE EDGE DISTANCE IS TO THE CENTER OF
 THE ANCHOR. PANEL SPAN NEEDS TO BE INCREASED AS
 REQUIRED.
 E) IF BOTTOM CONNECTION IS ON MASONRY, THEN THE MASONRY
 ANCHOR SPACING NEEDS TO BE USED. REVISE INSTALLATION
 SCHEDULE AS REQUIRED.
 F) CLARIFY HOW ARE SHUTTERS GOING TO BE INSTALLED
 VERTICALLY OR HORIZONTALLY. INSTALLATION SCHEDULE
 SUBMITTED SAYS VERTICAL BUT SHUTTER SPAN IS 122" WHICH
 IS ON THE HORIZONTAL INSTALLATION.
 NOTE: THIS ALSO AFFECTS THE CONNECTIONS TOP AND BOTTOM
 SINCE HEADERS CAN'T BE INSTALLED ON HORIZONTAL
 APPLICATIONS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712