Plan Review Notes
Plan Review Notes For Permit 08110110
Permit Number 08110110
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2009-01-27 09:15:271) IT APPEARS THAT RESPONSES HAVE BEEN PROVIDED TO
 PREVIOUS COMMENTS MADE BY THE FIRE RESCUE DEPARTMENT.
  
 2) NOTE # 3 BELOW DOOR SCHEDULE INDICATES ON PAGE A-1
 THAT "EXISTING GATES DESIGNATED TO BE PART OF AN EGRESS
 SYSTEM SHALL REMAIN UNLOCKED OR AUTOMATICALLY UNLOCK IN
 CASE OF FIRE DURING HOURS OF OPERATION". HOW DOES THIS
 AUTOMATIC UNLOCKING OCCUR.
  
 3) ON PAGE A-3 IT HAS BEEN DECLARED THAT OCCUPANT
 ACTIVITIES WILL INLCUDE "ADULT EDUCATION AND RELIGIOUS
 ACCESSORY USE". SOME INFORMATION SUGGESTS THAT THESE
 FACILITIES MAY BE USED FOR AN ADULT DAY CARE AND IS NOT
 DECLEARED ON THE PLANS. THIS INFORMATION IF TRUE NEEDS
 TO BE DECLARED ON THE PLANS. THE MINIMUM BUILDING AND
 FIRE CODE REQURIEMENTS SHALL BE MET FOR THE SPECIFIC
 OCCUPANCY TYPE AND USE. THE BUILDING AND ELECTRICAL
 PLAN REVIEWERS HAVE BOT DENIED THESE REVISED PLANS.
 PLEASE REVISE PLANS ACCORDINGLY AND ENSURE THAT ALL
 INFORMATION HAS BEEN PROVIDED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION