Date |
Text |
2009-01-23 16:36:26 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| 1-10. ADDRESSED. |
| |
| 11. FBC1008.1, THE DOOR CANNOT BLOCK MORE THAN HALF THE |
| REQUIRED WIDTH. PROVIDE DIMENSIONS TO SHOW COMPLIANCE. |
| |
| COMMENT NOT ADDRESSED. RESPONSE LETTER STATES THAT IT |
| IS STRUCTURALLY INFEASIBLE TO MODIFY THE EXISTING |
| STRUCTURE TO PROVIDE THE PROPER WIDTH, AND THIS IS AN |
| EXISTING CONDITION. NOTE THAT THIS APPEARS TO BE A |
| CHANGE OF OCCUPANCY WITH AN INCREASE IN OCCUPANT LOAD |
| AND THE CORRIDOR WIDTH IS BEING DECREASED DUE TO |
| INSTALLATION OF HANDRAILS. THEREFORE, THE STATEMENT |
| THAT ???THIS IS AN EXISTING CONDITION AND WE HAVE NOT |
| MADE IT WORSE??? IS NOT CORRECT. ALL MODIFICATIONS MUST |
| COMPLY WITH THE CODE, FBC1001.1, EVEN WHEN THE LEVEL OF |
| SAFETY/CODE COMPLIANCE IS KEPT THE SAME UNLESS |
| PROVISIONS MADE FOR THAT SITUATION IN THE CODE (OR |
| PROPOSED THROUGH ALTERNATE MATERIALS AND METHODS). SOME |
| WAYS WHICH THIS COULD BE ADDRESSED WOULD BE TO RECESS |
| THE DOORS, CHANGE THE DOOR LOCATION (IF AFFECTED BY THE |
| COLUMN), CHANGE THE PROPOSED RAILING LOCATION, INSWING |
| DOOR. SUGGESTIONS FOR RESOLUTION SHOULD BE THOROUGHLY |
| INVESTIGATED BY DOR AS FULL RESEARCH INTO EACH OF THESE |
| HYPOTHETICAL OPTIONS HAS NOT BEEN DONE. |
| |
| SCOPE CANNOT BE DETERMINED BECAUSE SHEETS A1 AND A3 ARE |
| NOT CONSISTENT REGARDING THE DOOR SWING AT ROOMS 110 |
| AND 109. LIFE SAFETY PLAN SHOWS THESE DOORS AS THE SAME |
| SWING AS THE DEMO PLAN. DEPENDING ON WHICH CHANGE IS |
| MADE, A DOOR IS POSSIBLY AFFECTED BY THE COLUMN OR |
| OTHER DOOR SWING. AT THIS POINT, IT CANNOT BE |
| DETERMINED WHAT NEEDS TO BE REVIEWED AS THE EXISTING |
| DOOR SWING AND PROPOSED DOOR SWING ARE NOT CLEAR. |
| |
| REGARDING CHANGING THE DOOR SWING WITHOUT COMPLYING |
| WITH THE CODE, ANY REQUEST TO PROPOSE AN ALTERNATIVE TO |
| THE CODE IS TO BE DONE THROUGH ALTERNATE MATERIALS AND |
| METHODS AND MUST BE MADE THROUGH A WRITTEN, USUALLY BY |
| LETTER STATING THE CODE SECTION CITED IN THE COMMENT |
| LIST, AND THE ARGUMENT IN FAVOR OF AN ALTERNATE METHOD. |
| IF THE CODE ALLOWS FOR AN EXCEPTION, THIS EXCEPTION |
| SHOULD BE INCORPORATED INTO THE PLAN. |
| |
| 12. SHOW MANEUVERING CLEARANCE FOR DOORS, FBC FIGURE |
| 11-25, PULL SIDE. |
| |
| RESPONSE LETTER STATES THAT THE AREA IS 5FT 8IN X 14FT. |
| IT IS NOT CLEAR WHAT DIMENSION YOU REFER TO AS THESE |
| DIMENSIONS ARE NOT NOTED ON THE PLAN. THE WALKWAY AREA |
| APPEARS TO BE 4FT 7IN DUE TO THE HANDRAIL, BUT AT THE |
| COLUMN IT IS NARROWER. PLEASE PROVIDE THAT DIMENSION. |
| NOTE THE REQUIREMENT OF 54IN IF THE DOOR HAS A CLOSER |
| FOR A SIDE APPROACH. AS THE ACTUAL DIMENSION IS LESS |
| THAN 60INCHES, FRONT APPROACH CANNOT BE USED WHERE |
| THERE IS A HANDRAIL. WHEN ALTERING THE DOOR, THE DOOR |
| ALTERATION IS TO COMPLY WITH FBC REQUIREMENTS, BOTH CH |
| 10 AND CH 11. |
| |
| GATE 116 DOES NOT COMPLY WITH MANEUVERING CLEARANCE |
| REQUIREMENT OF 18IN ON THE PULL SIDE, 12 IN ON THE PUSH |
| SIDE. IT IS NOT CLEAR IF DOOR 112 COMPLIES WITH THE |
| 12IN REQUIREMENT. |
| |
| 13-14. ADDRESSED. |
| |
| 15. NOTE ANY REQUIRED FIRE RESISTANCE RATINGS ON THE |
| PLAN. FOR INSTANCE, CORRIDOR PROTECTION MAY BE REQUIRED |
| FBC TABLE 1016.1. |
| |
| RESPONSE LETTER STATES FIRE RESISTANCE NOT REQUIRED FOR |
| THE CORRIDOR AS IT IS OPEN. IF THIS IS A TYPE IIIA |
| BUILDING, SHOULDN???T THE COLUMNS BE 1 HOUR, EXTERIOR |
| BEARING WALLS 2 HOUR, ETC. PER FBC TABLE 601? PLEASE |
| NOTE FIRE RATINGS ON THE PLAN TO AVOID FIELD CONFLICTS. |
| |
| 16-21. ADDRESSED. |
| |
| NEW COMMENTS: |
| |
| 22. THE OCCUPANT LOAD OF CLASSROOMS 108, 109, AND 110 |
| (WHICH ALL EXIT THROUGH THE RAMP SINCE THE OPEN |
| BREEZEWAY HAS NOW BEEN BLOCKED) EXCEEDS 50, SO TWO |
| EXITS ARE REQUIRED FBC1018.1. |
| |
| 23. ALTHOUGH THE GATE IN THE BREEZEWAY HAS BEEN NOTED |
| ???NOT AN EXIT???, IT IS STILL IN THE EXIT CORRIDOR AND |
| MUST COMPLY WITH THE REQUIREMENTS OF THE CODE. IF THE |
| GATE IS PERMANENTLY LOCKED, IT CREATES A DEAD END WHICH |
| EXCEEDS 20FEET FBC1016.3. |
| |
| 24. FBC1003.5.2, WHEN A CHANGE IN ELEVATION OF 12INCHES |
| OR LESS OCCURS IN AN EXIT ACCESS CORRIDOR, A RAMP SHALL |
| BE PROVIDED. THE STEP IS IN THE EXIT ACCESS CORRIDOR, |
| TWO EXITS ARE REQUIRED SO THE OCCUPANTS OF ROOMS 108, |
| 109, AND 110 NEED THIS AS A SECOND EXIT. EVEN IF THIS |
| IS MARKED AS NOT AN EXIT, THIS IS STILL LOCATED IN THE |
| EXIT ACCESS CORRIDOR. |
| |
| 25. THE EXTERIOR DOORS ARE BEING ALTERED, PLEASE |
| PROVIDE PRODUCT APPROVAL FOR THE DOORS, FBC EB 507.3, |
| FAC9B72. |
| |
| 26. IS THIS A CHANGE OF USE/OCCUPANCY? PLEASE SEE FBC |
| EB CHAPTER 8. SOME CODE REQUIREMENTS CANNOT BE |
| DETERMINED WITHOUT THIS INFORMATION. |
| |
| 27. WHAT IS THE AREA IN THE OPEN COURTYARD? PART OF IT |
| IS LABELED STORAGE, IS THIS CROSS SHAPED AREA A PART OF |
| THE EXISTING CLASSROOM BUILDING BEING RENOVATED? WHAT |
| ARE THE LINES WITH THE ARC? |
| |
| 28. ANOTHER REVIEWER HAS MADE NOTES THAT THIS AREA WILL |
| BE USED FOR ADULT DAY CARE, SEE FBC313.2.3. PLEASE NOTE |
| THAT OCCUPANT LOAD FBC1004 IS BASED ON ANTICIPATED |
| NUMBER OF PEOPLE BASED ON ACTIVITY, AND OCCUPANCY |
| CLASSIFICATION FBC CHAPTER 3 IS BASED ON CLASSIFICATION |
| AS TO USE. IT IS POSSIBLE TO HAVE AN ASSEMBLY TYPE OF |
| OCCUPANT LOAD IN ANOTHER OCCUPANCY CLASSIFICATION. |
| |
| 29. SEE ALSO FBC1033.6. IT CANNOT BE DETERMINED AT THIS |
| POINT IF THE DOORS WOULD BE CONSIDERED DIRECTLY TO THE |
| OUTSIDE; DO THE WINDOWS COMPLY WITH THE REQUIREMENT? IT |
| SEEMS THAT AT THIS POINT REQUIREMENTS ARE NOT CLEAR |
| BECAUSE OCCUPANCY DECLARED IS IN QUESTION. |
| |
| |