Plan Review Notes
Plan Review Notes For Permit 08110110
Permit Number 08110110
Review Stop B
Sequence Number 2
Notes
Date Text
2009-01-23 16:36:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1-10. ADDRESSED.
  
 11. FBC1008.1, THE DOOR CANNOT BLOCK MORE THAN HALF THE
 REQUIRED WIDTH. PROVIDE DIMENSIONS TO SHOW COMPLIANCE.
  
 COMMENT NOT ADDRESSED. RESPONSE LETTER STATES THAT IT
 IS STRUCTURALLY INFEASIBLE TO MODIFY THE EXISTING
 STRUCTURE TO PROVIDE THE PROPER WIDTH, AND THIS IS AN
 EXISTING CONDITION. NOTE THAT THIS APPEARS TO BE A
 CHANGE OF OCCUPANCY WITH AN INCREASE IN OCCUPANT LOAD
 AND THE CORRIDOR WIDTH IS BEING DECREASED DUE TO
 INSTALLATION OF HANDRAILS. THEREFORE, THE STATEMENT
 THAT ???THIS IS AN EXISTING CONDITION AND WE HAVE NOT
 MADE IT WORSE??? IS NOT CORRECT. ALL MODIFICATIONS MUST
 COMPLY WITH THE CODE, FBC1001.1, EVEN WHEN THE LEVEL OF
 SAFETY/CODE COMPLIANCE IS KEPT THE SAME UNLESS
 PROVISIONS MADE FOR THAT SITUATION IN THE CODE (OR
 PROPOSED THROUGH ALTERNATE MATERIALS AND METHODS). SOME
 WAYS WHICH THIS COULD BE ADDRESSED WOULD BE TO RECESS
 THE DOORS, CHANGE THE DOOR LOCATION (IF AFFECTED BY THE
 COLUMN), CHANGE THE PROPOSED RAILING LOCATION, INSWING
 DOOR. SUGGESTIONS FOR RESOLUTION SHOULD BE THOROUGHLY
 INVESTIGATED BY DOR AS FULL RESEARCH INTO EACH OF THESE
 HYPOTHETICAL OPTIONS HAS NOT BEEN DONE.
  
 SCOPE CANNOT BE DETERMINED BECAUSE SHEETS A1 AND A3 ARE
 NOT CONSISTENT REGARDING THE DOOR SWING AT ROOMS 110
 AND 109. LIFE SAFETY PLAN SHOWS THESE DOORS AS THE SAME
 SWING AS THE DEMO PLAN. DEPENDING ON WHICH CHANGE IS
 MADE, A DOOR IS POSSIBLY AFFECTED BY THE COLUMN OR
 OTHER DOOR SWING. AT THIS POINT, IT CANNOT BE
 DETERMINED WHAT NEEDS TO BE REVIEWED AS THE EXISTING
 DOOR SWING AND PROPOSED DOOR SWING ARE NOT CLEAR.
  
 REGARDING CHANGING THE DOOR SWING WITHOUT COMPLYING
 WITH THE CODE, ANY REQUEST TO PROPOSE AN ALTERNATIVE TO
 THE CODE IS TO BE DONE THROUGH ALTERNATE MATERIALS AND
 METHODS AND MUST BE MADE THROUGH A WRITTEN, USUALLY BY
 LETTER STATING THE CODE SECTION CITED IN THE COMMENT
 LIST, AND THE ARGUMENT IN FAVOR OF AN ALTERNATE METHOD.
 IF THE CODE ALLOWS FOR AN EXCEPTION, THIS EXCEPTION
 SHOULD BE INCORPORATED INTO THE PLAN.
  
 12. SHOW MANEUVERING CLEARANCE FOR DOORS, FBC FIGURE
 11-25, PULL SIDE.
  
 RESPONSE LETTER STATES THAT THE AREA IS 5FT 8IN X 14FT.
 IT IS NOT CLEAR WHAT DIMENSION YOU REFER TO AS THESE
 DIMENSIONS ARE NOT NOTED ON THE PLAN. THE WALKWAY AREA
 APPEARS TO BE 4FT 7IN DUE TO THE HANDRAIL, BUT AT THE
 COLUMN IT IS NARROWER. PLEASE PROVIDE THAT DIMENSION.
 NOTE THE REQUIREMENT OF 54IN IF THE DOOR HAS A CLOSER
 FOR A SIDE APPROACH. AS THE ACTUAL DIMENSION IS LESS
 THAN 60INCHES, FRONT APPROACH CANNOT BE USED WHERE
 THERE IS A HANDRAIL. WHEN ALTERING THE DOOR, THE DOOR
 ALTERATION IS TO COMPLY WITH FBC REQUIREMENTS, BOTH CH
 10 AND CH 11.
  
 GATE 116 DOES NOT COMPLY WITH MANEUVERING CLEARANCE
 REQUIREMENT OF 18IN ON THE PULL SIDE, 12 IN ON THE PUSH
 SIDE. IT IS NOT CLEAR IF DOOR 112 COMPLIES WITH THE
 12IN REQUIREMENT.
  
 13-14. ADDRESSED.
  
 15. NOTE ANY REQUIRED FIRE RESISTANCE RATINGS ON THE
 PLAN. FOR INSTANCE, CORRIDOR PROTECTION MAY BE REQUIRED
 FBC TABLE 1016.1.
  
 RESPONSE LETTER STATES FIRE RESISTANCE NOT REQUIRED FOR
 THE CORRIDOR AS IT IS OPEN. IF THIS IS A TYPE IIIA
 BUILDING, SHOULDN???T THE COLUMNS BE 1 HOUR, EXTERIOR
 BEARING WALLS 2 HOUR, ETC. PER FBC TABLE 601? PLEASE
 NOTE FIRE RATINGS ON THE PLAN TO AVOID FIELD CONFLICTS.
  
 16-21. ADDRESSED.
  
 NEW COMMENTS:
  
 22. THE OCCUPANT LOAD OF CLASSROOMS 108, 109, AND 110
 (WHICH ALL EXIT THROUGH THE RAMP SINCE THE OPEN
 BREEZEWAY HAS NOW BEEN BLOCKED) EXCEEDS 50, SO TWO
 EXITS ARE REQUIRED FBC1018.1.
  
 23. ALTHOUGH THE GATE IN THE BREEZEWAY HAS BEEN NOTED
 ???NOT AN EXIT???, IT IS STILL IN THE EXIT CORRIDOR AND
 MUST COMPLY WITH THE REQUIREMENTS OF THE CODE. IF THE
 GATE IS PERMANENTLY LOCKED, IT CREATES A DEAD END WHICH
 EXCEEDS 20FEET FBC1016.3.
  
 24. FBC1003.5.2, WHEN A CHANGE IN ELEVATION OF 12INCHES
 OR LESS OCCURS IN AN EXIT ACCESS CORRIDOR, A RAMP SHALL
 BE PROVIDED. THE STEP IS IN THE EXIT ACCESS CORRIDOR,
 TWO EXITS ARE REQUIRED SO THE OCCUPANTS OF ROOMS 108,
 109, AND 110 NEED THIS AS A SECOND EXIT. EVEN IF THIS
 IS MARKED AS NOT AN EXIT, THIS IS STILL LOCATED IN THE
 EXIT ACCESS CORRIDOR.
  
 25. THE EXTERIOR DOORS ARE BEING ALTERED, PLEASE
 PROVIDE PRODUCT APPROVAL FOR THE DOORS, FBC EB 507.3,
 FAC9B72.
  
 26. IS THIS A CHANGE OF USE/OCCUPANCY? PLEASE SEE FBC
 EB CHAPTER 8. SOME CODE REQUIREMENTS CANNOT BE
 DETERMINED WITHOUT THIS INFORMATION.
  
 27. WHAT IS THE AREA IN THE OPEN COURTYARD? PART OF IT
 IS LABELED STORAGE, IS THIS CROSS SHAPED AREA A PART OF
 THE EXISTING CLASSROOM BUILDING BEING RENOVATED? WHAT
 ARE THE LINES WITH THE ARC?
  
 28. ANOTHER REVIEWER HAS MADE NOTES THAT THIS AREA WILL
 BE USED FOR ADULT DAY CARE, SEE FBC313.2.3. PLEASE NOTE
 THAT OCCUPANT LOAD FBC1004 IS BASED ON ANTICIPATED
 NUMBER OF PEOPLE BASED ON ACTIVITY, AND OCCUPANCY
 CLASSIFICATION FBC CHAPTER 3 IS BASED ON CLASSIFICATION
 AS TO USE. IT IS POSSIBLE TO HAVE AN ASSEMBLY TYPE OF
 OCCUPANT LOAD IN ANOTHER OCCUPANCY CLASSIFICATION.
  
 29. SEE ALSO FBC1033.6. IT CANNOT BE DETERMINED AT THIS
 POINT IF THE DOORS WOULD BE CONSIDERED DIRECTLY TO THE
 OUTSIDE; DO THE WINDOWS COMPLY WITH THE REQUIREMENT? IT
 SEEMS THAT AT THIS POINT REQUIREMENTS ARE NOT CLEAR
 BECAUSE OCCUPANCY DECLARED IS IN QUESTION.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved