Plan Review Notes
Plan Review Notes For Permit 08110110
Permit Number 08110110
Review Stop P
Sequence Number 1
Notes
Date Text
2008-12-02 16:56:07DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 EXISTING BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1, ALL SHEETS SEALED BY THE ARCHITECT OF RECORD ARE
 REQUIRED TO HAVE THE SIGNATURE OF THE DESIGN
 PROFESSIONAL. IT APPEARS THAT INITIALS HAVE BEEN USED
 IN PLACE OF THE SIGNATURE. IF THE INITIALS ARE INDEED
 THE LEGAL SIGNATURE OF THE DESIGN PROFESSIONAL, THEN A
 SIGNED, SEALED, NOTORIZED LETTER INDICATING THE LEGAL
 SIGNATURE OF THE ARCHITECT SHALL BE SUBMITTED FOR OUR
 RECORDS. FAC 61G1-16.003, 61G1-16.004(5) & FS 481.2055.
  
 2. SUBMIT AN EXISTING FLOOR PLAN SO THE EXTENT OF THE
 WORK INDICATED CAN BE VERIFIED. SECTION 106.1.2.
  
 3. SHT A-1 SHOW THE ROOM NUMBERS THAT CORRESPOND TO THE
 ROOMS INDICATED ON THE APPLICATION FOR PERMIT. SECTIONS
 106.1.1 & 106.1.2.
  
 4. SHT A-1 TOILET ROOMS SHOW IMAGES OF W/C'S IN THE
 WOMEN'S AND MEN'S TOILET ROOMS AND AN IMAGE OF A LAV IN
 THE MEN'S TOILET SUPERIMPOSED OVER THE W/C AND LAV. ARE
 THE FIXTURES BEING DELETED OR MOVED FROM THERE ORIGINAL
 LOCATION? PLEASE CLARIFY. IF FIXTURES ARE DELETED THEN
 CALCULATION FOR MINIMUM FACILITIES PER TABLES 1004.1.2
 & 403.1 ARE REQUIRED TO INDICATE COMPLIANCE WITH
 REQUIRED FIXTURES. SECTION 106.1.1. ARE THERE REQUIRED
 DRINKING FOUNTAINS?
  
 5. SHT A-1 INDICATES CODE REQUIREMENTS WITH 2006
 REVISIONS. CODE SHALL ALSO INCLUDE THE 2007 REVISIONS
 AS WELL AS THE 2005 REVISIONS. SECTION 106.1.1.
  
 6. INDICATE THE LEVEL OF ALTERATION AS REQUIRE IN
 SECTION 301 OF THE EXISTING BUILDING CODE.
  
 7. SHT A-1 INDICATES 4 ABANDONED GAS BASE BOARD HEATERS
 AND A NEW 30 GALLON GAS WATER HEATER. A SEPARATE GAS
 PERMIT IS REQUIRED THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 8. SHT P-1 THE SANITARY RISER DIAGRAM SHOWS AN EXISTING
 W/C & LAV BY THE CLASSROOM SINK THAT IS NOT SHOWN ON
 THE FLOOR PLAN. PLEASE CLARIFY. SHOW THE EXISTING
 TOILET ROOM ON THE FLOOR PLAN. SECTIONS 106.1.1,
 106.1.2 & 701.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved