2008-11-26 13:12:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PROVIDE A DEMO PLAN WHICH SHOULD INCLUDE EXISTING
 FLOOR PLAN. SCOPE IS NOT CLEAR. IT IS NOT CLEAR WHICH
 WALLS ARE EXISTING, WHICH ARE NEW.
  
 2. PLEASE NOTE THAT THE FLOOR PLAN SHOWN ON A1 DOES NOT
 IDENTIFY DOORS, ROOMS, OR CORRIDORS. FOR INSTANCE,
 THERE ARE FIVE DIFFERENT ROOMS LABELED "EXISTING
 CLASSROOM". THERE ARE MANY DOORS BUT THEY ARE NOT
 LABELED, AND AS THE ROOMS AND CORRIDORS ARE NOT LABELED
 IT IS DIFFICULT FOR ME TO IDENTIFY WHICH DOOR, ROOM, OR
 CORRIDOR IS REFERRED TO IN THE COMMENT. ROOM
 DESIGNATION NUMBERS, OR A DOOR SCHEDULE, WOULD BE
 HELPFUL.
  
 3. PROVIDE A CODE SUMMARY; BUILDING TYPE FBC6, BUILDING
 HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, OCCUPANCY
 CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY.
  
 4. DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 5. GOVERNING CODE SHOULD INCLUDE 2007
 REVISIONS/SUPPLEMENTS (EFFECTIVE JULY 1, 2007).
  
 6. SHOW CORRIDOR WIDTHS. FBC11-4.8.6, FBC10.
  
 7. DECLARE SQUARE FOOT AREA AND OCCUPANT LOAD FOR EACH
 ROOM. FBC10.
  
 8. A DOOR IS SHOWN AS SWINGING AGAINST THE DIRECTION OF
 TRAVEL. SEE COMMENT 7; CLARIFY REQUIREMENTS FBC1008.1.
 9. A 1" SLOPE IS SHOWN IN THE CORRIDOR. SPECIFY THE
 WIDTH, FBC10, FBC11.
  
 10. A 4" ELEVATION CHANGE IS SHOWN AT A DOOR. SEE
 FBC1003.5.2, FBC1104.3.8.
  
 11. FBC1008.1, THE DOOR CANNOT BLOCK MORE THAN HALF THE
 REQUIRED WIDTH. PROVIDE DIMESIONS TO SHOW COMPLIANCE.
  
 12. SHOW MANEUVERING CLEARANCE FOR DOORS, FBC FIGURE
 11-25, PULL SIDE.
  
 13. A2, DETAIL LABELED AS "GUARDRAIL". NOTE THAT A
 GUARDRAIL IS REQUIRED TO BE 42", BUT THIS IS SHOWN AS
 36". IS A GUARDRAIL REQUIRED? FBC1012.1. IS THIS A
 HANDRAIL RATHER THAN A GUARDRAIL?
  
 14. A TYPICAL INTERIOR PARTITION DETAIL WAS PROVIDED.
 HOWEVER, IT IS NOT CLEAR WHAT THIS IS FOR; EXISTING OR
 PROPOSED? ALSO (WALL LEGEND) NOTE THAT THE GRAPHIC FOR
 THE BLOCK WALL DOES NOT MATCH THE GRAPHIC USED FOR THE
 EXTERIOR WALL, AND THE GRAPHIC FOR THE FRAME WALL DOES
 NOT APPEAR ON THE FLOOR PLAN. SEE OTHER COMMENTS
 REGARDING SCOPE OF WORK.
  
 15. NOTE ANY REQUIRED FIRE RESISTANCE RATINGS ON THE
 PLAN. FOR INSTANCE, CORRIDOR PROTECTION MAY BE REQUIED
 FBC TABLE 1016.1.
  
 16. WHAT DO THE DASHED LINES REPRESENT? THEY APPEAR IN
 TWO DIFFERENT EXISTING CLASSROOMS.
  
 17. A3, LIFE SAFETY PLAN, THE PATH OF TRAVEL SHOULD BE
 MEASURED ALONG THE PATH OF ANTICIPATED TRAVEL. IT IS
 SHOWN GOING THROUGH THE CENTER OF THE ROOM, WHERE A
 CLASSROOM WOULD NORMALLY HAVE CHAIRS AND DESKS. PATH OF
 TRAVEL SHOULD BE SHOWN ALONG THE PERIMETER OF THE ROOM.
  
 18. PROVIDE MORE INFORMATION REGARDING THE EXIT
 DISCHARGE. THE LIFE SAFETY PLAN MEASURES TO THE RAMP
 BASE. IS THIS THE OUTSIDE? A DOOR IS SHOWN ADJACENT TO
 THE RAMP IN THE HALLWAY. COVERED WALKWAYS SHOULD BE
 INCLUDED IN PATH OF TRAVEL. FBC1002. PLAN SHOULD SHOW
 WHERE THE OCCUPANT WILL LEAVE THE BUILDING (INCLUDING
 COVERED WALKWAYS).
  
 20. DOES THE BUILDING HAVE A FIRE ALARM? SEE
 FBC11-4.28. NOTE THAT A VISUAL SIGNAL IS REQUIRED IN
 THE RESTROOMS; NONE SHOWN.
  
 21. THE PROPOSED CHANGE OF DOOR SWING APPEARS TO
 INTERFERE WITH THE DOOR SWING OF THE ADJACENT DOOR,
 FBC1008. PLEASE REVISE.
  
  
  