Plan Review Notes For Permit 08110006 |
Permit Number |
08110006 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-01-14 10:26:10 | ****CORRECTIONS**** | | ****REVISED 1/16/9**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. A NOTE HAS BEEN ADDED TO THE UL ASSEMBLY, "OPTIONAL | | CONT. CAULKING". PLEASE SHOW HOW THE RATED WALLS WILL | | COMPLY WITH FBC708.4 OR FBC706.4 CONTINUITY. RATED | | WALLS NOT NOTED AS FIRE PARTITIONS OR FIRE BARRIERS. | | | | 2. THE PURPOSE, CONSTRUCTION, AND LOCATION OF DETAIL 22 | | IS NOT CLEAR BASED ON THE INFORMATION PROVIDED. IT IS | | MY UNDERSTANDING THAT THIS DETAIL IS TO ADDRESS THE | | REQUIREMENT FOR SUPPORTS AT 4' OC FOR FULL HEIGHT FIRE | | RATED WALLS WHICH ARE STRUCTURALLY UNSUPPORTED AT THE | | TOP OF THE WALL. THE PURPOSE OF THE DETAIL IS NOT | | CLEAR; IT NOTES CATS AT 4' OC. FIRE RATED WALLS SHOULD | | HAVE A HEAD OF WALL DETAIL SPECIFIED FOR FIRE | | RESISTANCE. STRUCTURAL SUPPORT DETAILS SHOULD BE NOTED | | AS SUCH AND MATERIALS USED AND FASTENING SHOULD BE | | STATED PLEASE REVISE, FBC*106, FBC708, FBC16. | | | | |
|