2008-11-10 13:53:47 | |
| |
| |
| ** DENIED REVIEW ** |
| |
| 1) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE |
| CALCULATIONS PER 13-415.2,13-415.2.ABC.1.1,.1.2. |
| PLEASE SEE THE LPC SUBMITTED DO NOT COORDINATE WITH |
| PLANS AND FIXTURE LEGEND. PLEASE SEE THE FIXTURE LEGEND |
| AND THE WATTAGES SHOWN. PLEASE SEE THE CALCULATIONS |
| SUBMITTED ONLY INDICATE TWO FIXTURES. |
| |
| 2) NOTE: PLEASE SEE 408.36, 240.21 AND 310.16 AS THE |
| TAPPED CONDUCTORS ON THE SECONDARY SIDE OF THE |
| TRANSFORMER ARE REQUIRED TO TERMINATE IN OVER CURRENT |
| PROTECTION. |
| |
| 3) NOTE: PLEASE INDICATE THE CONTINUOUS LOADS AT 125%. |
| 230.42,215.3 ETC. |
| PLEASE SEE 422.13 FOR ANY STORAGE TYPE WATER HEATERS. |
| |
| |
| |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |