Plan Review Notes
Plan Review Notes For Permit 08110006
Permit Number 08110006
Review Stop E
Sequence Number 1
Notes
Date Text
2008-11-10 13:53:47 
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2,13-415.2.ABC.1.1,.1.2.
 PLEASE SEE THE LPC SUBMITTED DO NOT COORDINATE WITH
 PLANS AND FIXTURE LEGEND. PLEASE SEE THE FIXTURE LEGEND
 AND THE WATTAGES SHOWN. PLEASE SEE THE CALCULATIONS
 SUBMITTED ONLY INDICATE TWO FIXTURES.
  
 2) NOTE: PLEASE SEE 408.36, 240.21 AND 310.16 AS THE
 TAPPED CONDUCTORS ON THE SECONDARY SIDE OF THE
 TRANSFORMER ARE REQUIRED TO TERMINATE IN OVER CURRENT
 PROTECTION.
  
 3) NOTE: PLEASE INDICATE THE CONTINUOUS LOADS AT 125%.
 230.42,215.3 ETC.
 PLEASE SEE 422.13 FOR ANY STORAGE TYPE WATER HEATERS.
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  