2008-11-01 11:16:09 | |
| |
| DENIED |
| |
| 1) PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL |
| COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 & 2007 |
| AMENDMENTS PER 106.1.1 FBC* |
| |
| 2) IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING |
| MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF |
| ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND |
| STATE ALONG WITH THE TYPE OF CONSTRUCTION AND OCCUPANCY |
| ON THE DRAWINGS |
| |
| 3) PROVIDE WIND DESIGN DATA ON DRAWINGS PER 1603.1.4 |
| FBC |
| |
| 4) EXTERIOR WALL ARE SUBJECT TO WIND LOADS, PROVIDE THE |
| DESIGN PRESSURES FOR THE NEW OPENING |
| |
| 5) PROVIDE BUILDING PLAN VIEW TO DETERMINE LOCATION OF |
| OPENINGS AND THEIR RESPECTIVE WIND ZONE |
| |
| 6) BUILDING ELEVATION TO INCLUDE MEAN ROOF HEIGHT |
| |
| 7) PROVIDE INFORMATION ON HURRICANE STRAPS OR |
| CONNECTORS THAT WILL BE USED |
| |
| 8) THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. |
| |
| 9) THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9B-72 |
| (PRODUCT APPROVALS) SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| |
| 10) NO PRODUCT APPROVALS WERE SUBMITTED FOR THE |
| CONNECTORS AND STRAPS. IN LUE OF PRODUCT APPROVALS |
| STRAPS/CONNECTORS MAY BE LISTED IN A SCHEDULE ON THE |
| DRAWINGS COMPLETE WITH THE STATEWIDE PRODUCT APPROVAL |
| NUMBERS OR SUBMIT SIMPSON TIE?S COMPLETE FLORIDA INDEX |
| WITH CONNECTORS TO BE USED HIGHLIGHTED |
| |