Plan Review Notes For Permit 08100687 |
Permit Number |
08100687 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-11-04 08:49:00 | RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW CHECKLIST. | | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 | | REVISIONS. | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | FLORIDA STATUTE. | | | | 2- SINCE ALL OPENINGS ARE GOING TO HAVE SHUTTERS, THEN | | SPECIFY HOW COMPLYING WITH THE EMERGENCY EGRESS | | REQUIREMENTS OF SEC. R310.4 OF 2004 FLORIDA RESIDENTIAL | | CODE. | | | | 3- INSTALLATION SCHEDULE INDICATES THE MINIMUM EDGE | | DISTANCE TO BE 3". ANCHOR SCHEDULES ON SHEETS 13 AND 14 | | ARE FOR 3 1/2" EDGE DISTANCE. NEED TO REDUCE ANCHOR | | SPACING AS REQUIRED BY EDGE DISTANCE VERSUS SPACING FOR | | ANCHORS TABLE ON SHEET 14. REVISE AS REQUIRED. | | ***NOTES: A) EDGE DISTANCE EXCLUDES STUCCO FINISH. B) | | COORDINATE PANEL SPAN COLUMN WITH EDGE DISTANCE COLUMN. | | | | 4- TYPE OF TAPCON TO BE USED TO MATCH TYPE OF TAPCON | | SPECIFIED ON STORM SHUTTERS DRAWINGS SHEET 14. | | | | 5- OPENINGS #4 AND #10 CALLS FOR CONNECTION TYPE "E" AT | | BOTTOM. DRAWINGS SUBMITTED ARE HIGHLIGHTING CONNECTION | | TYPE "I" ON SHEET 7. CLARIFY WHICH IS THE ACTUAL | | CONNECTION TYPE THAT IS GOING TO BE USED TO AVOID | | CONFLICTS. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 | | |
|