2008-11-04 08:49:00RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 2- SINCE ALL OPENINGS ARE GOING TO HAVE SHUTTERS, THEN
 SPECIFY HOW COMPLYING WITH THE EMERGENCY EGRESS
 REQUIREMENTS OF SEC. R310.4 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 3- INSTALLATION SCHEDULE INDICATES THE MINIMUM EDGE
 DISTANCE TO BE 3". ANCHOR SCHEDULES ON SHEETS 13 AND 14
 ARE FOR 3 1/2" EDGE DISTANCE. NEED TO REDUCE ANCHOR
 SPACING AS REQUIRED BY EDGE DISTANCE VERSUS SPACING FOR
 ANCHORS TABLE ON SHEET 14. REVISE AS REQUIRED.
 ***NOTES: A) EDGE DISTANCE EXCLUDES STUCCO FINISH. B)
 COORDINATE PANEL SPAN COLUMN WITH EDGE DISTANCE COLUMN.
  
 4- TYPE OF TAPCON TO BE USED TO MATCH TYPE OF TAPCON
 SPECIFIED ON STORM SHUTTERS DRAWINGS SHEET 14.
  
 5- OPENINGS #4 AND #10 CALLS FOR CONNECTION TYPE "E" AT
 BOTTOM. DRAWINGS SUBMITTED ARE HIGHLIGHTING CONNECTION
 TYPE "I" ON SHEET 7. CLARIFY WHICH IS THE ACTUAL
 CONNECTION TYPE THAT IS GOING TO BE USED TO AVOID
 CONFLICTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER