Date |
Text |
2008-11-04 13:20:10 | |
| |
| |
| |
| ** DENIED REVIEW ** |
| |
| 1) NOTE: |
| |
| 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES AS ADOPTED |
| BY FS 553.73 ARE LISTED ON PLANS ACCORDINGLY. FOR |
| EXAMPLE COVER SHEET INDICATES NFPA-70 ( NATIONAL |
| ELECTRICAL CODE) AS THE 2002 EDITION. THIS CODE HAS NOT |
| BEEN IN EFFECT IN THE STATE OF FLORIDA SINCE DECEMBER |
| 8TH, 2006. |
| PLANS SHOULD NOTE AS FOLLOWS. |
| 2004 FBC W/ 2007 REVISIONS. |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| 2005 NFPA-70. |
| |
| ** SOME OF THESE ARE SHOWN ON ELECTRICAL PLANS HOWEVER |
| COORDINATION WITH OTHER PLANS IS NEEDED. ELECTRICAL |
| PLANS DO NOT LIST SPECIFIC ADOPTED CODES |
| |
| 3) NOTE: PLEASE INCLUDE NEW LIGHTING CONTROLS FOR NEW |
| AREAS PER 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| ** THIS IS FOR NEW INSTALLED ONLY. |
| ** PLEASE VERIFY CONTROLS AS THE SYMBOL LEGEND CALL FOR |
| NEW SWITCHES, YET NONE ARE SHOWN AS EXISTING OR NEW. |
| |
| 4) NOTE: PLEASE INCLUDE LIGHTING PERFORMANCE |
| CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1,.1.2. |
| ** NEW BEING INSTALLED. |
| ** PLEASE BE SURE TO COMPLETE FIXTURE LEGEND WITH |
| SPECIFIC FIXTURES. |
| |
| 5) NOTE: PLEASE BE SURE TO LIST THE REQUIRED LOCATIONS, |
| LEVELS AND HEIGHTS OF FIRE ALARM DEVICES PER FBC |
| 11-4.28.1, .2 AND 3. QUOTING ANSI OR OTHER CODES IN |
| LIEU OF SPECIFIC CODE REQUIRED DETAIL IS NOT PERMITTED. |
| |
| ** IT IS IMPORTANT TO KNOW AS THERE IS SOME INFORMATION |
| NOT YET SUBMITTED THERE MAY VERY WELL BE NEW COMMENTS |
| ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS |
| TIME. |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |