Plan Review Notes
Plan Review Notes For Permit 08100683
Permit Number 08100683
Review Stop E
Sequence Number 1
Notes
Date Text
2008-11-04 13:20:10 
  
  
  
 ** DENIED REVIEW **
  
 1) NOTE:
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES AS ADOPTED
 BY FS 553.73 ARE LISTED ON PLANS ACCORDINGLY. FOR
 EXAMPLE COVER SHEET INDICATES NFPA-70 ( NATIONAL
 ELECTRICAL CODE) AS THE 2002 EDITION. THIS CODE HAS NOT
 BEEN IN EFFECT IN THE STATE OF FLORIDA SINCE DECEMBER
 8TH, 2006.
 PLANS SHOULD NOTE AS FOLLOWS.
 2004 FBC W/ 2007 REVISIONS.
 2003 NFPA-101
 2002 NFPA-72
 2005 NFPA-70.
  
 ** SOME OF THESE ARE SHOWN ON ELECTRICAL PLANS HOWEVER
 COORDINATION WITH OTHER PLANS IS NEEDED. ELECTRICAL
 PLANS DO NOT LIST SPECIFIC ADOPTED CODES
  
 3) NOTE: PLEASE INCLUDE NEW LIGHTING CONTROLS FOR NEW
 AREAS PER 13-415.1.ABC.1.1, .1.2 AND .1.3.
 ** THIS IS FOR NEW INSTALLED ONLY.
 ** PLEASE VERIFY CONTROLS AS THE SYMBOL LEGEND CALL FOR
 NEW SWITCHES, YET NONE ARE SHOWN AS EXISTING OR NEW.
  
 4) NOTE: PLEASE INCLUDE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1,.1.2.
 ** NEW BEING INSTALLED.
 ** PLEASE BE SURE TO COMPLETE FIXTURE LEGEND WITH
 SPECIFIC FIXTURES.
  
 5) NOTE: PLEASE BE SURE TO LIST THE REQUIRED LOCATIONS,
 LEVELS AND HEIGHTS OF FIRE ALARM DEVICES PER FBC
 11-4.28.1, .2 AND 3. QUOTING ANSI OR OTHER CODES IN
 LIEU OF SPECIFIC CODE REQUIRED DETAIL IS NOT PERMITTED.
  
 ** IT IS IMPORTANT TO KNOW AS THERE IS SOME INFORMATION
 NOT YET SUBMITTED THERE MAY VERY WELL BE NEW COMMENTS
 ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS
 TIME.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved