Plan Review Notes
Plan Review Notes For Permit 08100660
Permit Number 08100660
Review Stop E
Sequence Number 2
Notes
Date Text
2009-02-04 10:30:08 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ADDRESS ON THE PLAN DOES NOT MATCH THE ADDRESS
 ON THE APPLICATION, CORRELATE SAME. 106.1 FBC
  
 2} THE PLAN SUBMITTED DOES NOT SEEM TO BE THE SAME PLAN
 AS WAS SUBMITTED 11/14/08 AS THE COMMENTS MADE DO NOT
 RELATE TO THIS PLAN.SEE COMMENT #1.
  
 3} PLEASE LOCATE ALL SERVICE EQUIPMENT ON A SITE OR
 FLOOR PLAN, METER ENCLOSURE, DISCONNECTS AND PANELS, SO
 THAT COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE
 REVIEWED. A DISCONNECT MAY BE REQUIRED PER
 230.70(A)(1).
  
 4} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.*** THIS
 COMMENT IS MADE BECAUSE THE NEW PANEL WITH WOULD BE
 SUBJECT TO LINE FAULT CURRENT AS THE FIRST MEANS OF
 DISCONNECT.
  
 5} PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE
 EQUIPMENT TO BE INSTALLED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  