Plan Review Notes
Plan Review Notes For Permit 08100660
Permit Number 08100660
Review Stop E
Sequence Number 1
Notes
Date Text
2008-11-18 08:43:03 
  
  
 ** FAILED REVIEW **
  
  
 1) NOTE: PLEASE INDICATE THE LOCATION OF THE PANEL.
 110.26,240.24, 408.36
  
 2) NOTE: PLANS SUBMITTED CONTAIN A TITLE BLOCK FROM AN
 ENGINEERING FIRM. PLANS MUST BE SIGNED, DATED AND
 SEALED FORM THAT ENGINEERING FIRM PER FS 471.025, FAC
 61G15-23.002.
  
 3) NOTE: MISSING EQUIPMENT GROUNDING AFTER THE FIRST
 MEANS OF DISCONNECT PER 250.110,250.122.
  
 4) NOTE: NEEDS TO HAVE TWO GROUND RODS. 250.50, 250.56
  
 5) NOTE: RISER INDICATES AN OVER HEAD SERVICE HOWEVER
 THE NOTE ON RISER MENTIONS TO BASE OF POLE WHICH WOULD
 LEND TO AN UNDERGROUND SERVICE.
 PLEASE COORDINATE WHICH ONE IT WILL BE AND REVISE AS
 NEEDED.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  