| ** FAILED REVIEW ** |
| |
| |
| 1) NOTE: PLEASE INDICATE THE LOCATION OF THE PANEL. |
| 110.26,240.24, 408.36 |
| |
| 2) NOTE: PLANS SUBMITTED CONTAIN A TITLE BLOCK FROM AN |
| ENGINEERING FIRM. PLANS MUST BE SIGNED, DATED AND |
| SEALED FORM THAT ENGINEERING FIRM PER FS 471.025, FAC |
| 61G15-23.002. |
| |
| 3) NOTE: MISSING EQUIPMENT GROUNDING AFTER THE FIRST |
| MEANS OF DISCONNECT PER 250.110,250.122. |
| |
| 4) NOTE: NEEDS TO HAVE TWO GROUND RODS. 250.50, 250.56 |
| |
| 5) NOTE: RISER INDICATES AN OVER HEAD SERVICE HOWEVER |
| THE NOTE ON RISER MENTIONS TO BASE OF POLE WHICH WOULD |
| LEND TO AN UNDERGROUND SERVICE. |
| PLEASE COORDINATE WHICH ONE IT WILL BE AND REVISE AS |
| NEEDED. |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |