2008-11-07 09:50:36 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. COVER SHEET IS INDICATING THE WRONG CODE CYCLE. |
| PLEASE DECLARE THE CORRECT GOVERNING CODE (FBC-2004 |
| WITH 2007 REVISIONS). PER (W.P.B. AS AMENDED) SECTION |
| 106.5 RETENTION OF CONSTRUCTION DOCUMENTS. |
| |
| 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004 |
| EXISTING BUILDING CHAPTER 3. |
| |
| 3. SHEET L-3 SPECIFICATIONS, FOOD SERVICE NOTES (2) |
| SCOPE OF WORK STATES THAT A WATER LINE WILL BE |
| FURNISHED AND INSTALLED FOR A NEW REFRIGERATOR WITH ICE |
| MAKER, FILTERED WATER COOLER, AND COFFEE MAKER HOWEVER |
| THERE IS NO CLEAR LOCATION OF THESE ITEMS ON ANY PLAN |
| SHEETS. PLEASE CLEARLY INDICATE THE LOCATION OF THESE |
| ITEMS AND PROVIDE THE FOLLOWING PER FBC-2004 CHAPTER 1, |
| SECTION 106.3.5.1.3, PLUMBING (3)(10)(13): AN ISOMETRIC |
| POTABLE WATER RISER DIAGRAM IS REQUIRED FOR THE |
| PROPOSED WORK FOR BOTH THE HOT AND COLD WATER |
| INDICATING THE PIPE SIZES, VALVE LOCATIONS, LOCATION OF |
| THE WATER SUPPLY LINE WITH BACKFLOW PREVENTER **608, |
| THERMAL EXPANSION CONTROL FOR THE WATER HEATER (IF |
| APPLICABLE) **607.3, AND LOCATION OF THE WATER-HAMMER |
| ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED |
| (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS) |
| **604.9. |
| |
| 4. PLEASE CLARIFY ON THE RESUBMITTAL IF THERE IS AN |
| EXISTING DRINKING FOUNTAIN LOCATED IN THE COMMON AREA |
| THAT IS ADA COMPLIANT OR IS THE WATER COOLER INDICATED |
| ON SHEET L-3 THIS REQUIRED DRINKING FOUNTAIN PER |
| FBC-2004 PLUMBING TABLE 403.1 MINIMUM NUMBER OF |
| REQUIRED PLUMBING FIXTURES A DRINKING FOUNTAIN IS |
| REQUIRED FOR A BUSSINESS OCCUPANCY (1 PER 100). PLEASE |
| KNOW THAT IF THE WATER COOLER IS IN FACT THE REQUIRED |
| DRINKING FOUNTAIN THE FOLLOWING IS REQUIRED PER THE |
| FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE |
| SECTIONS. |
| |
| **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING |
| INFORMATION) |
| 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| MAXIMUM. |
| 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN |
| 3" OF THE FRONT OF FOUNTAIN. |
| 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE |
| MOUNTED NEAR FRONT EDGE. |
| 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| SPACE. |
| 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| *PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| |