Plan Review Notes
Plan Review Notes For Permit 08100611
Permit Number 08100611
Review Stop P
Sequence Number 1
Notes
Date Text
2008-11-07 09:50:36PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. COVER SHEET IS INDICATING THE WRONG CODE CYCLE.
 PLEASE DECLARE THE CORRECT GOVERNING CODE (FBC-2004
 WITH 2007 REVISIONS). PER (W.P.B. AS AMENDED) SECTION
 106.5 RETENTION OF CONSTRUCTION DOCUMENTS.
  
 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 3. SHEET L-3 SPECIFICATIONS, FOOD SERVICE NOTES (2)
 SCOPE OF WORK STATES THAT A WATER LINE WILL BE
 FURNISHED AND INSTALLED FOR A NEW REFRIGERATOR WITH ICE
 MAKER, FILTERED WATER COOLER, AND COFFEE MAKER HOWEVER
 THERE IS NO CLEAR LOCATION OF THESE ITEMS ON ANY PLAN
 SHEETS. PLEASE CLEARLY INDICATE THE LOCATION OF THESE
 ITEMS AND PROVIDE THE FOLLOWING PER FBC-2004 CHAPTER 1,
 SECTION 106.3.5.1.3, PLUMBING (3)(10)(13): AN ISOMETRIC
 POTABLE WATER RISER DIAGRAM IS REQUIRED FOR THE
 PROPOSED WORK FOR BOTH THE HOT AND COLD WATER
 INDICATING THE PIPE SIZES, VALVE LOCATIONS, LOCATION OF
 THE WATER SUPPLY LINE WITH BACKFLOW PREVENTER **608,
 THERMAL EXPANSION CONTROL FOR THE WATER HEATER (IF
 APPLICABLE) **607.3, AND LOCATION OF THE WATER-HAMMER
 ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED
 (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS)
 **604.9.
  
 4. PLEASE CLARIFY ON THE RESUBMITTAL IF THERE IS AN
 EXISTING DRINKING FOUNTAIN LOCATED IN THE COMMON AREA
 THAT IS ADA COMPLIANT OR IS THE WATER COOLER INDICATED
 ON SHEET L-3 THIS REQUIRED DRINKING FOUNTAIN PER
 FBC-2004 PLUMBING TABLE 403.1 MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES A DRINKING FOUNTAIN IS
 REQUIRED FOR A BUSSINESS OCCUPANCY (1 PER 100). PLEASE
 KNOW THAT IF THE WATER COOLER IS IN FACT THE REQUIRED
 DRINKING FOUNTAIN THE FOLLOWING IS REQUIRED PER THE
 FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN
 3" OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  