Plan Review Notes
Plan Review Notes For Permit 08100611
Permit Number 08100611
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-11-06 15:05:55***DENIED***
  
 1) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 ALARM REMODEL.
  
 2) PLEASE SHOW FIRE SPRINKLER LAYOUT PF ALTERED AREAS.
 ADDITIONALLY, SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL.
  
 3) ILLUSTRATE THE LOCATIONS OF REQUIRED 2A-10B,C RATED
 FIRE EXTINGUISHERS.
  
 4) JOB SITE TO BE CLEANED OF EXCESS DEBRIS DAILY OR
 MORE FREQUENTLY TO ENSURE SAFE OPERATION.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756