2008-11-04 09:59:16 | |
| |
| |
| |
| ** DENIED REVIEW ** |
| |
| 1) NOTE: PLEASE SEE THE TITLE BLOCK IS INDICATING |
| APPLIED DESIGN INITIATIVE LLC WHICH IS REQUIRED TO BE |
| LICENSED IN THE STATE O FLORIDA PER FLORIDA STATUTES |
| 481.219. PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| 61G1-16.004 WHICH REQUIRES LICENSE NUMBER TO BE LISTED |
| ON TITLE BLOCKS. IF THE WORK IS SOLELY THROUGH THE |
| RESPONSIBLE ARCHITECT AS LISTED PLEASE EITHER INCLUDE |
| LICENSING OR REMOVE FROM TITLE BLOCKS. |
| ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADE |
| WHICH INDICATE THIS INFORMATION. |
| |
| 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES AS ADOPTED |
| BY FS 553.73 ARE LISTED ON PLANS ACCORDINGLY. FOR |
| EXAMPLE COVER SHEET INDICATES NFPA-70 ( NATIONAL |
| ELECTRICAL CODE) AS THE 2002 EDITION. THIS CODE HAS NOT |
| BEEN IN EFFECT IN THE STATE OF FLORIDA SINCE DECEMBER |
| 8TH, 2006. |
| PLANS SHOULD NOTE AS FOLLOWS. |
| 2004 FBC W/ 2007 REVISIONS. |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| 2005 NFPA-70. |
| |
| ** SOME OF THESE ARE SHOWN ON ELECTRICAL PLANS HOWEVER |
| COORDINATION WITH OTHER PLANS IS NEEDED. |
| |
| 3) NOTE: PLEASE LIST THE MAXIMUM TIMES ON OCCUPANCY |
| SENSORS/OVER RIDES AS NOTED ON SYMBOL LEGEND. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2. |
| |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |