Plan Review Notes
Plan Review Notes For Permit 08100611
Permit Number 08100611
Review Stop E
Sequence Number 1
Notes
Date Text
2008-11-04 09:59:16 
  
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THE TITLE BLOCK IS INDICATING
 APPLIED DESIGN INITIATIVE LLC WHICH IS REQUIRED TO BE
 LICENSED IN THE STATE O FLORIDA PER FLORIDA STATUTES
 481.219. PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 WHICH REQUIRES LICENSE NUMBER TO BE LISTED
 ON TITLE BLOCKS. IF THE WORK IS SOLELY THROUGH THE
 RESPONSIBLE ARCHITECT AS LISTED PLEASE EITHER INCLUDE
 LICENSING OR REMOVE FROM TITLE BLOCKS.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADE
 WHICH INDICATE THIS INFORMATION.
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES AS ADOPTED
 BY FS 553.73 ARE LISTED ON PLANS ACCORDINGLY. FOR
 EXAMPLE COVER SHEET INDICATES NFPA-70 ( NATIONAL
 ELECTRICAL CODE) AS THE 2002 EDITION. THIS CODE HAS NOT
 BEEN IN EFFECT IN THE STATE OF FLORIDA SINCE DECEMBER
 8TH, 2006.
 PLANS SHOULD NOTE AS FOLLOWS.
 2004 FBC W/ 2007 REVISIONS.
 2003 NFPA-101
 2002 NFPA-72
 2005 NFPA-70.
  
 ** SOME OF THESE ARE SHOWN ON ELECTRICAL PLANS HOWEVER
 COORDINATION WITH OTHER PLANS IS NEEDED.
  
 3) NOTE: PLEASE LIST THE MAXIMUM TIMES ON OCCUPANCY
 SENSORS/OVER RIDES AS NOTED ON SYMBOL LEGEND.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  