2008-10-30 09:57:44PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SHOW ON A/C PLAN 3.1 HOW THE AIR HANDLER IS TO BE
 SERVICED WHEN THERE IS NO DOOR TO THE AREA. SEE 2004
 FBC/R M1305.1 AND M1601.3.3.
  
 2) PLAN 3.1 STATES REMOVE AND REPLACE EXISTING DUCTS IN
 ALL HOUSE. PLEASE SHOW THE DUCT DESIGN WITH ALL SIZES
 SUPPLY AND RETURN ALSO THE CFM'S, PER 2004 FBC /R
 M1601.1 AND FBC 13-610.1.ABC.1 AND WPB AMEND. 106.3.5.4
 (10). SEE 2004 FBC/R M1602.4 REGARDING RETURN AIR
 REQUIREMENTS.
  
 3) SHOW ON PLAN AN EQUIPMENT SCHEDULE FOR EQUIPMENT
 BEING REPLACED AIR HANDLER (AND CONDENSER UNIT IF BEING
 REPLACED), PER 2004 WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;