2008-10-30 09:57:44 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) SHOW ON A/C PLAN 3.1 HOW THE AIR HANDLER IS TO BE | | SERVICED WHEN THERE IS NO DOOR TO THE AREA. SEE 2004 | | FBC/R M1305.1 AND M1601.3.3. | | | | 2) PLAN 3.1 STATES REMOVE AND REPLACE EXISTING DUCTS IN | | ALL HOUSE. PLEASE SHOW THE DUCT DESIGN WITH ALL SIZES | | SUPPLY AND RETURN ALSO THE CFM'S, PER 2004 FBC /R | | M1601.1 AND FBC 13-610.1.ABC.1 AND WPB AMEND. 106.3.5.4 | | (10). SEE 2004 FBC/R M1602.4 REGARDING RETURN AIR | | REQUIREMENTS. | | | | 3) SHOW ON PLAN AN EQUIPMENT SCHEDULE FOR EQUIPMENT | | BEING REPLACED AIR HANDLER (AND CONDENSER UNIT IF BEING | | REPLACED), PER 2004 WPB AMEND. 106.3.5.4 (10). | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|