Plan Review Notes
Plan Review Notes For Permit 08100604
Permit Number 08100604
Review Stop E
Sequence Number 1
Notes
Date Text
2008-11-05 10:23:02 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE SERVICE ON SHEET 4.1 IS SHOWN AS AN EXISTING BUT
 MUST BE CORRECTED AS IT IS A LIFE SAFETY ISSUE. THERE
 IS A GROUNDING ELECTRODE CONDUCTOR AT THE METER AND A
 GROUNDING ELECTRODE SYSTEM SHOWN AT THE PANEL WITH A
 DISCONNECT IN BETWEEN THE TWO IN VIOLATION OF
 250.24(A)(5) LOAD-SIDE GROUNDING CONNECTIONS A
 GROUNDING CONNECTION SHALL NOT BE MADE TO ANY GROUNDED
 CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECTING
 MEANS EXCEPT AS OTHERWISE PERMITTED IN THIS ARTICLE.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225, 240 AND 230 CAN BE
 REVIEWED.
  
 3} INDICATE HOW THE EQUIPMENT GROUND IS RAN AND WHERE
 IT ORIGINATES, ON THE SERVICE RISER DIAGRAM SEE COMMENT
 #1
  
 4} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE NOTE #2 TO REFLECT THIS
 CHANGE.
  
 5} ELECTRICAL NOTE #3 IS INCORRECT REGARDING GFCI
 PROTECTION AT THE SINK***210.8(A) DWELLING UNITS ALL
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL. (6) KITCHENS ? WHERE THE RECEPTACLES ARE
 INSTALLED TO SERVE THE COUNTERTOP SURFACES. PLEASE
 CORRECT.
  
 6} ELECTRICAL NOTE #4 REGARDING THE CIRCUITING FOR
 SMOKE ALARMS IS NOT A VIOLATION BUT IT SHOULD BE NOTED
 THAT THE CIRCUIT MUST COMPLY WITH 210.12 AND BE AFCI
 PROTECTED. ALSO SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD. IF USING DETECTORS
 INDICATE THE LOCATIONS OF THE SOUNDING DEVICES.
  
 7} BEDROOM #3 MUST COMPLY WITH 210.12, NOTE SAME ON THE
 PLANS.
  
 8} IF THE CONDENSING UNIT IS BEING REPLACED TO MATCH
 THE AHU, LOCATE SAME ON PLANS, ALSO SHOW COMPLIANCE
 WITH THE REQUIRED DISCONNECT PER 440.14, RECEPTACLE PER
 210.63.
  
 9} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATION NUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE. 61G15-23.002 SEAL, SIGNATURE AND
 DATE SHALL BE AFFIXED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  