Plan Review Notes For Permit 08100604 |
Permit Number |
08100604 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-11-10 16:50:23 | 2004 FBC W/2007 REVISIONS | | LEVEL 2 ALTERATION | | | | DENIED BY BUILDING | | | | 1) THE CONSTRUCTION TYPE AND CODE EDITION SPECIFIED ON | | THE COVERSHEET ARE INCORRECT. SPECIFY THE 2004 FBC | | SECTION 602.5 AND TYPE V-B CONSTRUCTION. | | | | 2) THE SCOPE OF WORK ON SHEET 1.1 SPECIFIES REPLACING 2 | | WINDOWS AND ON SHEET 1.2 THREE WINDOWS ARE TO BE | | REPLACED. PLEASE CORRECT. | | | | 3) THE BATHROOM WINDOW IS INCORRECTLY SPECIFIED AS AN | | EGRESS WINDOW ON THE WINDOW SCHEDULE ON SHEET 1.2. | | PLEASE CORRECT. | | | | 4) THE NOA (03-0717.03) SPECIFIED FOR WINDOWS 2 AND 3 | | IN THE WINDOW SCHEDULE IS EXPIRED. PLEASE CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|