Notes |
Date |
Text |
2008-10-30 14:34:13 | | | | | DENIED | | | | 1) PROVIDE PRODUCT APPROVALS FOR MULLIONS THAT WILL BE | | USED BETWEEN FIXED WINDOW UNITS OR STATE THAT MULLIONS | | ARE FIXED IN PLACE AND A STRUCTURAL PART OF THE | | BUILDING. | | | | 2) THE FIXED WINDOW UNIT IN THE CENTER OF THE 2 SMALLER | | UNITS IS OF A SIZE THAT DOES NOT MEET THE DESIGN | | PRESSURES FOR THE "B" TYPE GLAZING THAT WAS CHOSEN. SEE | | SHEET 2 OF 5 IN THE NOA. | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 | | |
|