Plan Review Notes
Plan Review Notes For Permit 08100551
Permit Number 08100551
Review Stop P
Sequence Number 1
Notes
Date Text
2008-11-03 13:38:18PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE "FLORIDA SOLAR ENERGY CENTER, APPROVED SOLAR
 ENERGY SYSTEM" SHEET IS INDICATING SEVENTEEN DIFFERENT
 MODEL NUMBERS FOR THE COLLECTOR MANUFACTURER AND THREE
 CONTROLLER MANUFACTURER'S. CLEARLY INDICATE ON THE
 RESUBMITTAL WHICH MODEL NUMBER COLLECTOR AND CONTROLLER
 ARE BEING USED ON THE PROPOSED SOLAR POOL. PER FBC-2004
 CHAPTER 1, (W.P.B.) AS AMENDED SECTION 106.1.2
 ADDITIONAL DATA.
  
 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED SECTION
 *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
 *THE CONTRACTOR OF RECORD MAY BE THE DESIGN
 PROFESSIONAL IF EXEMPTIONS UNDER FLORIDA STATUTES
 471.003(H) APPLY.
  
 3. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW FOR
 (9) 4' X 12' PANELS. THE VALUE ON THE PERMIT
 APPLICATION MUST INCLUDE THE TOTAL COST OF LABOR,
 MATERIALS AND DESIGN.
 PER (W.P.B AS AMENDED) SECTION 108.3 BUILDING PERMIT
 VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF BUILDING, ALTERATION,
 STRUCTURAL, ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED.
  
 4. PER FS 713.13 (1) THRU (6): A NOTICE OF COMMENCEMENT
 IS REQUIRED FROM THE - PALM BEACH COUNTY COURTHOUSE -
 4TH FLOOR RECORDING DEPT. 205 N. DIXIE HWY., BEFORE THE
 FIRST INSPECTION. PER FS 713.13 (2): IF THE IMPROVEMENT
 DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS VOID AND OF NO FURTHER EFFECT.
  
 END OF COMMENTS:
  
 *IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  