2009-03-16 13:02:26*****DENIED*****
  
  
  
 05. WHAT EQUIPMENT AND/OR PROCESSES WILL BE USED AT THE
 NEW MEZZANINE LEVEL? YOUR RESPONSE WAS THAT THE SPACE
 IS FOR VIDEO GAME STORAGE AND SOME REPAIR; HOWEVER
 RESPONSE TO PREVIOUS ITEMS 6 THRU 9 INDICATES THAT THE
 STAIRS TO THE MEZZANINE ARE TO BE REMOVED THE DRAWINGS
 AND WILL BE REMOVED FROM THE IMPROVEMENT. WHERE WILL
 THE STORAGE OF THESE ITEMS BE LOCATED.
  
 10. SHOW THE LOCATION OF EXIT LIGHTS, EMERGENCY LIGHTS,
 AND FIRE EXTINGUISHER(S) FOR THE NEW FLOOR PLAN. COULD
 NOT LOCATE THE LOCATION OF THE FIRE EXTINGUISHER(S)
  
 NEW COMMENT:
  
 AA. IT APPEARS THAT EGRESSING AT THE REAR EXIT HAS TO
 DONE THROUGH AN OFFICE. PLEASE EXPLAIN AS PER NFPA 101,
 2003 EDITION HOW THIS ARRANGEMENT IS ACCEPTABLE.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE THE COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW