Plan Review Notes For Permit 08100531 |
Permit Number |
08100531 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-03-16 13:02:26 | *****DENIED***** | | | | | | | | 05. WHAT EQUIPMENT AND/OR PROCESSES WILL BE USED AT THE | | NEW MEZZANINE LEVEL? YOUR RESPONSE WAS THAT THE SPACE | | IS FOR VIDEO GAME STORAGE AND SOME REPAIR; HOWEVER | | RESPONSE TO PREVIOUS ITEMS 6 THRU 9 INDICATES THAT THE | | STAIRS TO THE MEZZANINE ARE TO BE REMOVED THE DRAWINGS | | AND WILL BE REMOVED FROM THE IMPROVEMENT. WHERE WILL | | THE STORAGE OF THESE ITEMS BE LOCATED. | | | | 10. SHOW THE LOCATION OF EXIT LIGHTS, EMERGENCY LIGHTS, | | AND FIRE EXTINGUISHER(S) FOR THE NEW FLOOR PLAN. COULD | | NOT LOCATE THE LOCATION OF THE FIRE EXTINGUISHER(S) | | | | NEW COMMENT: | | | | AA. IT APPEARS THAT EGRESSING AT THE REAR EXIT HAS TO | | DONE THROUGH AN OFFICE. PLEASE EXPLAIN AS PER NFPA 101, | | 2003 EDITION HOW THIS ARRANGEMENT IS ACCEPTABLE. | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE THE COMMENT WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|