2009-03-11 10:44:31 | ** DENIED 2ND RESUB ** |
| |
| *** PLEASE KNOW THAT SEVERAL NOTES FROM PREVIOUS REVIEW |
| ARE STILL IN NEED OF ADDRESSING. THERE ARE ALSO SEVERAL |
| NEW NOTES AS SOME INFORMATION WHICH IS ONLY NOW |
| SUBMITTED DOES NOT MEET MINIMUM CODE COMPLIANCE. NOTES |
| BELOW WILL BE MARKED FOR NEW COMMENTS. NOTES BELOW WILL |
| ALSO BE MARKED FOR PREVIOUS REVIEW COMMENTS. |
| |
| 1) NOTE: PREVIOUS REVIEW: PLEASE SUBMIT PLANS SHOWING |
| MINIMUM CODE COMPLIANCE FOR LIGHTING CONTROLS FOR NEW |
| PER FBC 13-415.1.ABC.1.1, .1.2. THE RESPONSE LETTER |
| MENTIONS *NOTES* WERE ADDED TO PLANS. THE PLANS DO NOT |
| CONTAIN ANY NOTES WITH RESPECT TO MINIMUM LIGHTING |
| CONTROLS. IN EITHER CASE PLACING NOTES ON THE PLANS IN |
| LIEU OF DETAILS IS NOT PERMITTED. PLEASE BE SURE TO ADD |
| THE SPECIFIC TYPE OF CONTROLS, TIMES ETC. |
| |
| 2) NOTE: PREVIOUS REVIEW: PLEASE SEE 13-415.2, |
| 13-415.2.ABC.1.1 AND .1.2. THE PREVIOUS REVIEW |
| REQUESTED TO SHOW LIGHTING PERFORMANCE CALCULATIONS PER |
| THE SECTIONS GIVEN. THE RESPONSE MENTIONS THESE ITEMS |
| ARE SHOWN ON PLANS HOWEVER THERE ARE NO LIGHTING |
| PERFORMANCE CALCULATIONS PER THE SECTIONS GIVEN SHOWN |
| ON PLANS. |
| |
| 3) NOTE: NEW COMMENT: PLEASE SEE NEW RISER WHICH NOW |
| SHOWS THE MAIN SERVICE WITH A 100AMP FEED TO A 100AMP |
| PANEL YET THE PANEL SCHEDULE INDICATES A 200AMP PANEL. |
| THESE DO NOT CORRELATE. |
| PLEASE ALSO SEE THE LOAD CALCULATIONS FOR THIS UNIT IS |
| NOT CODE COMPLIANT. THE RECEPTACLE LOAD FOR EXAMPLE |
| INDICATE SONLY FOUR(4) TOTAL RECEPTACLES AT 180VA EACH. |
| HOWEVER PLEASE TAKE A LOOK AT THE PLANS THERE IS A |
| SUBSTANTIAL AMOUNT OF MORE RECEPTACLES THAN FOUR. |
| 220.12,220.14,220.44 ETC. |
| |
| 4) NOTE: NEW COMMENT: PLEASE SEE THE TOTAL LOAD |
| CALCULATIONS AS EACH BAY INDICATES THE SAME EXACT LOADS |
| WHICH IS NOT POSSIBLE. SEVERAL OF THESE UNITS HAVE BEEN |
| BUILT OUT WITH A SUBSTANTIAL AMOUNT OF MORE LOAD THAN |
| WHAT IS SHOWN. |
| PLEASE ALSO SEE THE TOTAL OF THE LOAD CALCULATIONS |
| WHICH INDICATES THE LOAD AT 440AMPS ON A 600AMP |
| SERVICE. HOWEVER THE RISER CLEARLY INDICATES THIS MAIN |
| SERVICE AS 600AMP EQUIPMENT WITH 400AMP FUSES. THIS |
| WOULD TAKE THE LOAD OVER THE RATING OF THE OVER CURRENT |
| PROTECTION PROVIDED. THIS IS NOT ONLY NOT PERMITTED IT |
| IS UNSAFE AND DOES NOT MEET: |
| 220,230.70,230.71,230.76,230.79, 240.4, 310.16,110.14, |
| ETC. THERE TOO MANY SECTIONS TO NOTE. THE LOAD MAY NOT |
| EXCEED THE SERVICE RATING. |
| |
| 5) NOTE: NEW COMMENT: PLEASE SEE THE OCCUPANCY |
| CLASSIFICATION IS NOW LISTED AS *F*. WHAT WILL BE |
| MANUFACTURED IN THIS LOCATION? THERE ARE CONCERNS OVER |
| THE TYPE OF MANUFACTURING AND PRODUCTS OF STORAGE ETC |
| WITH RESPECT TO ELECTRICAL PERTAINING TO POSSIBLE CLASS |
| AND DIVISION LOCATIONS. |
| PLEASE BE SURE TO SEE NEC 500 (ALL) FOR POSSIBLE CODE |
| REQUIREMENTS. |
| |
| 6) NOTE: PLEASE BE AWARE OF FS 553.80(2)(B) WITH |
| RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. THERE |
| ARE SECTIONS WHICH HAVE BEEN REPEATED A SECOND TIME. |
| |
| ** THERE ARE STILL SEVERAL UNANSWERED ITEMS OR |
| CORRECTIONS WHICH NEED TO BE MADE WHICH MAY CREATE NEW |
| COMMENTS. |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |